2 Diesel Generators 900KVA connected to the bus bar for
essential load as an alternative for power taken from
11/440V 3KVA Transformer supplying this bus bar. my
question here is in the event of power failure on 11KV side
can I feed the power to 11 KV bus by using the same
transformer as reverse feed, what will be the inrush
current???
Answer Posted / joy
Your generator will be damaged. The reason being
that the transformer impedance as well as
impedeance of the entire 11kv side will be loaded
on the generator. Besides the inrush current which
the transformer will take when you charge it. This
will lead to the dropping of pf of the generator,
leading to the heating of its windings. Also you
have to make sure there are no chances of the
"normal" 11kv source being re applied when the
generator is being used to charge the 11kv side. Or
else the generator will experience a shearing of
its rotor.
| Is This Answer Correct ? | 7 Yes | 1 No |
Post New Answer View All Answers
When we use 3 terminal resistor?
Why have to use copper cable for local isolator to motor ?
What is mean by STUB protection?
what are the different methods for the starting of a synchronous motor.
132/66kv sub-station procation ?
What is difference between Sample test and Routine test in safety standard?
What is the physical significance of phase.. i.e. what is exactly the meaning in layman's language.. 1 phase, 3 phase etc ???
Is it possible to implement Restricted Earth Fault protection for a transformer without neutral CT?
WHAT ARE THE DATAS REQUIRED FOR PROTECTION AND METERING AND CONTROL AND LOGIC PREPARATION,HOW TO STUDY THE PROTECTION AND METERING?
Write the current equation in series RLC circuits.
A commercial Building is designed with 14th floor levels with indoor substation of three phase transformer with rated capacity of 1000 Kva.The transformer delivered 65% of its rated capacity at 0.67 power factor lagging.Because of low power factor, the power customer was penalized and certain cost was charged accordingly based on every point percentage lower than 85%.This situation may repeatedly happen on the succeding energy bills of power customer.The power customer is desired to improve its historical power factor of 0.67 lagging and no further penalty be impose by the local power company on the next bill. Q: Identify the appropriate solution you want to offer to Client?.Justify SCIENTIFICALLY and MATHEMATICALLY the principles behind the solution.
Do any one know exacatly when the results for NHPC held on 8th march 09 for engineering trainees will be released ?. if so please post it, i'm eager to know it.
draw singleline diagram of star to delta and dol starters
Why we use Electrical energy rather than any other type of energy, mostly? Explain behavior of open secondary CT and short circuited secondary PT in energized condition?
advantage of motor design on higher power factor . normally motors are designed for .8 power factor. what is advantage of designing at .88 power factor