2 Diesel Generators 900KVA connected to the bus bar for
essential load as an alternative for power taken from
11/440V 3KVA Transformer supplying this bus bar. my
question here is in the event of power failure on 11KV side
can I feed the power to 11 KV bus by using the same
transformer as reverse feed, what will be the inrush
current???
Answer Posted / joy
Your generator will be damaged. The reason being
that the transformer impedance as well as
impedeance of the entire 11kv side will be loaded
on the generator. Besides the inrush current which
the transformer will take when you charge it. This
will lead to the dropping of pf of the generator,
leading to the heating of its windings. Also you
have to make sure there are no chances of the
"normal" 11kv source being re applied when the
generator is being used to charge the 11kv side. Or
else the generator will experience a shearing of
its rotor.
| Is This Answer Correct ? | 7 Yes | 1 No |
Post New Answer View All Answers
how to get electrical supervisour certificate in gujarat
what are the difference between PLC and embedded
What are the applications of different multistage amplifiers?Plz also write advantages of these amplifiers? Thaaaaaaaaanx
why the value of k is more in shell typr transformers?
As per standard, transformer body earthing and other Equipment earthing (Equipment earthing) did not connect. but in LT side termination we are doing metal glanding in both side Transformer to PCC Panel through armoured cable, now X'mer body earthing and PCC Pane earthing (Equipment earthing) both are connect.is this safe for X'mer or other equipment?
List out the the types of Mounting Light fixture?
what clearance required for 4.5 mva dry type transformer?
How Self works in DG set
Explain the working of variable frequency transformer?
why do we carry out winding resistance test?
explain PV modules in solar energy generation.
how can tell us the AC indoor or outdoor which Tr and formulls
Disadventage of cable-gland earthing if any ?
What is the formula formula for Busbar sizing and what are the things to be consider for Busbar Calculation?
how can we phase identification in a distribution line,how we recognise that which phase is coming for a house hold connection.help me............