How the Transformer oil testing is done & Why oil dielectric
goes LOW & what is solution for that ??
Answer Posted / saroj
TRF oil is tested in a glass pot where high voltage,KV is
applied between two electrodes and sparking at electrode to
be observed. For good oil , it comes about 40~60KV/mm .If
it comes lower then filteration is required. Those TRF
having tap changing is frequently required it is
recommended to do filteration in once in year.Also its
value goes low because of moisture ingress in oil .
| Is This Answer Correct ? | 5 Yes | 1 No |
Post New Answer View All Answers
which pump used in STP
What is the role of power pack in substation protection system?
In an ACB shunt trip coil and undervoltage coil operated normally( breaker open and charged). But closing coil not operating untill manually discharge and recharging. Any help.
what is the effect of earth on capacitance in 3-phase and 1- phase transmission line?
What is Electrical Grade Aluminum for Tubular BusBars. i am confused between 6063 and T6 or T5 and what is BS 2898 and BS 159?
How can calculate the rating of a servo stabilizer for given a specific load
what is the criteria for selecting fuse rating in 1phase, 2phase & 3phase welding sets?
what are the advantages and disadvantages of speed control of 3 phase induction motor by varying frequency explain with drawing
does any one know where we can purchase insulation oil for high voltage oil filled cables
'documenˁ
I HAVE A 50A MCCB AS PER DESIGN LINE WIRE CONNECT UPWORD SIDE AND LOAD IS CONNECTED TO DOWNWARD SIDE TO THE MCCB.IF NOW ANY ONE CHANGE SUPPLY & LOAD(WISEVERSA) WHAT HAPPENS ? DOES MCCB OPERATION OR WORKING FUNCTION NORMAL IF YES THAN WHY THERE ARE MARKED LINE & LOAD ON MCCB.
how to calculate the tarriff for an industry whose kva demand is 10 mva
what work will do diffrential realay DG set
What is kirchoff ’s current law (kcl)?
i have 3500 amp load and select current transformer and perches.how i calculate .please understand