A Generator is in running condition and Rotor earth fault
alarm is coming.How to check on line(i.e in running
condition) whether there is actual earth fault in rotor or
not.
Answer Posted / kk
Rotor earth relay have 2
stage. One 4 alarm & other 4
trip. One can check the
bridge o/p voltage(mV) &
compare with comissioning
time value.
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
why high speed tripping relay is used in protection circuit why not normal relay
ASTM D 3455 - Standard Test Methods for Compatibility of Construction Material with Electrical Insulating Oil of Petroleum Origin has been used for Testing Transformer Oils with a product placed in it. Aged Control Oil has a Power Factor of 0.032% at 100°C. Aged Oil with a Test component has a Power Factor of 0.093% at 100°. Is this increase acceptable? If not why? How much increase is acceptable?
During regenerative breaking= A rotating magnetic field is reversed B slip is positive C torque is positive D slip is negative
what does a string of resistors in a series will do?
Has someone here done a sizing for a generator (3 phase), its for a pumping station. If you have an example for standby/duty and both running (I) star delta (ii) Soft Starter.
Describe Non I.S. Earth System and why is it used?
how to find three phase complex power in per unit and MVA?
How can we find out LT UG cable fault (size,from-4*25mm sqr to 4*300mm sqr)? How mani types UG cable faults?
How to calculate flow of water delivered by pump when pressure & size of pipe line is given
how to find out 3 phase complex power in per unit in unbalanced system?
12.5 tons a/c is their how much kva generator can recommend to the customer.
we have one oven for 12 zone we are installed ir lamp in oven we control load from thyrister and 0 to 5vdc so our zone no 8 getting bright in fraction of second so what we do.. Please answer
what is the Transformer Impedence?How can calculate?
what is the AC Plant and how can do the work with parts and picture tell us 150 Tr
defult setting in p220 micom motor proction relay for 11kv,640kw,f.l.a.-40a,1440rpm ht motor?