dear friends,

we are use 130 hp load run with 0.98 power factor ( 38KVAR
capacitor connected ). if we need improve the the power
factor to 1 (unity). how much kvar capacitor to be add. have
any formula? please share with me.

Answer Posted / jitendra

130*746=96.98kw
kvar=kw(tan pi1-tan pi2)
kvar=96.98(.2030-0)
= 19.68 Kvar

Is This Answer Correct ?    5 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Where can i get practical knowledge of solar system?

1078


I am getting above 60 V as open delta voltage against single phase unit ICT at tertiary delta formed and ICT getting trippped on NDR. ICT tested and found in order. PTs provided on tertiary are tested and in order. what may be the reason?

1404


How Can You Relate Power Engineering With Electrical Engineering?

833


Whether 3 phase induction motorwith 100 hp capacity , Amp 160 for which sensitive earth fault relay , type CTUM 15 can be used?

1086


What about electrical Units. discrive in detail

1608






What are dependent sources?

750


in shunt clippers why a resistor is used in sereis with the input

1621


what is the function of bearing in dc mchine" and where it is placed

2184


A Generator is in running condition and Rotor earth fault alarm is coming.How to check on line(i.e in running condition) whether there is actual earth fault in rotor or not.

1561


What are the advantages and disadvantages of short-pitched winding?

710


I HAVE A INCOMING 100A MCCB TPN 25KA, CABLE LENGHT OF 80M 70MM CABLE SIZE FROM MAIN SUBBOARD TO NEW DB.BASE ON THE FAULT LEVEL SETTING OF 45KA.I WOULD LIKE TO FIND OUT 25KA ENOUGH KA. APPRECIATE IF SOMEBODY CAN ASSIST ME WITH FORMULA FOR THIS. FRM: JEFF

3638


What are Contactors? How they works and what its highest rating?

1652


Explain how you intend to work under pressure to meet up with deadline target?

2035


what is rating boiler

1655


What is the difference between cylindrical-type and sandwich-type winding?

1082