we are use 130 hp load run with 0.98 power factor ( 38KVAR
capacitor connected ). if we need improve the the power
factor to 1 (unity). how much kvar capacitor to be add. have
any formula? please share with me.
Answer Posted / jitendra
130*746=96.98kw
kvar=kw(tan pi1-tan pi2)
kvar=96.98(.2030-0)
= 19.68 Kvar
| Is This Answer Correct ? | 5 Yes | 1 No |