Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

how will you calculate rated Primary and Secondary voltage and
Current for 2500 KVA, 11kv/443V Transformer

Answer Posted / rajutadhikari

Rated current on HV side:
Irhv = P/ (1.732 * V) = 2500k/ (1.732*11k) = 131.22 Amps

Rated current on LV side:
Irlv = P/ (1.732 * V) = 2500k/ (1.732*0.443k) = 3258.28 Amps

Is This Answer Correct ?    12 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

We have 250 KW x 2 motors, which are load from 25% to 100% varying load in every minute , so how can we compansate the power factor. pl give your opinions on the above subject.

1824


we have provided 30 nos. relay contacts in panel.I want to know how do we do the numbering for the relay contacts as per any applicable standards

1962


What is the percentage loss for aluminium wire for HT line more than 11KVa

2057


what is mean by Digital Logic Meter (DLM)

2322


how much excitation voltage required to generate 1mw power?

1992


in battery charging room we find two fuses (one in positive other in negative cables ).why it is so?one fuse is ore than sufficient?

2208


What OPGW is better than Microwave or PLCC???

4087


what about the power of wattmeter at starting and loding?

2047


What does the kvar means?

1142


DG SET BLOCK DIGRAM

2238


what is smart grid? why we use it? explain in detals bcoz i want give presentatin from it....

1901


May I know how much values to be set for earth fault, over current and short circuit values at 11kv side? I have 11kv van 1250amps rating. Present it's taking load 80amps?

1444


why motor range is available 22kv,30kv,37kv,45kv and so on? why motor range is not available 21kv,24,25,26,27kv and so on?

2748


What is the rating factor for copper cable ( Specific value according to the type of laying ) & the voltage drop?

1811


EXPLIAN THE IMPORTANCE OF POLY PHASE CIRCUIT.

2101