what is pf. how to calculate capacitor bank value to
maintain unity pf.
Answer Posted / vekuva
KVAR= KW(TAN PHI 1 - TAN PHI 2 )
WHERE PHI 1 = EXISTING POWER FACTOR ANGLE i.e., COS^¯1(p.f1)
PHI 2 = REQUIRED POWER FACTOR ANGLE i.e., COS^¯1(p.f2)
p.f 1 = EXISTING POWER FACTOR
p.f 2 = REQUIRED POWER FACTOR
| Is This Answer Correct ? | 5 Yes | 2 No |
Post New Answer View All Answers
Draw the vector diagram and condition for the following: 1) Dyn1 2) Ynd0 3) YnYn0
What is capacitance?
what is ps impedance test
What is notching in dc machine?
transformer spections :: input voltage 0-110-230v; output volage 0-10-12-14v; amp=3A using CRNO CORE, capcaity=50VA primary turns = ? ; secondry turns =?
what should be the no load current for 3 phase ac motors ranging from 5 kw to 1000kw?
why we cannot protect 100% winding of an alternator by using differential protection?
After taking shutdown of 11kv feeder, if you see 5kv by phasing stick in the cable side, is it possible to close earth switch in cable.
can u give me a brief idea about power line carrier communication ??
Why do we use copper cable for HT Supply and why not Aluminium?
What are the basic components of the feedback control system?
How to calculate ant test the burden of Current transformer
Can any one give an explanation about rating factors of cable? if we are laying the cable on the air with an temp 15 degree then rating factors will be 1.15 and if we are laying the cable on the air an temp 60 degree then rating factor will be 0.76 please describe it and what is the difference between rating factor and derating factor?
What is cathode ray oscilloscope (cro)?
what is the purpose of bypass mode in energy lighting transformer?