how can we measure the pressure in underground cooling
water pipeline by using pressure transmitter?what about the
tapping position?

Answer Posted / sam

You can install the PT anywhere on the pipe. It is best to
install on top in crude and slurry application but to
measure water you can install any where, even under the pipe.
If you install on the side or under the pipe fill the
impulse line with water then do a zero on the PT before you
do the final span calibration. Also remember that the
calibration you do on the PT must be exactly the same as to
what your DCS or SCADA faceplate have been scaled to. In
other words if you calibrate the PT for 0 to 20Bar you must
make sure the faceplate in the CCR are also scaled to 0 to
20bar.
Good luck

Is This Answer Correct ?    5 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

How to control flow variations in magnetic flow maters..... When i will provide proper earthing?

1926


Which tank weighing system is better to install (Accuracy point of view) 1) Tank weighing system with 3 load cell or 2) Tank weighing system with 4 Load cell

845


How to work togather like sov,limit switch,proxy switch and booster in xv

3850


Please can anybody help for control valve sizing step by step procedure?

1756


What is the difference between modbus,fieldbus & profibus

2004






how do we commission inergen system?

1525


what is RTV function in in process control?

2725


what is the reason while warning lamp is on while the engine is cranking?

1709


Explain bernoulli’s theorem. State its application.

781


Tell about your IFFCO plant visit.

1743


Why mixer nd grinder Is example of constant torque load not variable torque load ???

1615


PLEASE PROVIDE SAMPLES OF CHEVRON SKILL TESTS

3554


How many ohms are required for proper earthing?

732


What is the exact differences between HART,FOUNDATION FIELDBUS,PROFIBUS?

3094


Can please tell mi about SIOS, PRM, SERVER, and what is the diference between PIN LAN, PCS LAN,APC Server, and please send the Doc if possible for referance,mail id patil_amit17@yahoo.com

1572