how can we measure the pressure in underground cooling
water pipeline by using pressure transmitter?what about the
tapping position?
Answer Posted / sam
You can install the PT anywhere on the pipe. It is best to
install on top in crude and slurry application but to
measure water you can install any where, even under the pipe.
If you install on the side or under the pipe fill the
impulse line with water then do a zero on the PT before you
do the final span calibration. Also remember that the
calibration you do on the PT must be exactly the same as to
what your DCS or SCADA faceplate have been scaled to. In
other words if you calibrate the PT for 0 to 20Bar you must
make sure the faceplate in the CCR are also scaled to 0 to
20bar.
Good luck
Is This Answer Correct ? | 5 Yes | 0 No |
Post New Answer View All Answers
How to control flow variations in magnetic flow maters..... When i will provide proper earthing?
Which tank weighing system is better to install (Accuracy point of view) 1) Tank weighing system with 3 load cell or 2) Tank weighing system with 4 Load cell
How to work togather like sov,limit switch,proxy switch and booster in xv
Please can anybody help for control valve sizing step by step procedure?
What is the difference between modbus,fieldbus & profibus
how do we commission inergen system?
what is RTV function in in process control?
what is the reason while warning lamp is on while the engine is cranking?
Explain bernoulli’s theorem. State its application.
Tell about your IFFCO plant visit.
Why mixer nd grinder Is example of constant torque load not variable torque load ???
PLEASE PROVIDE SAMPLES OF CHEVRON SKILL TESTS
How many ohms are required for proper earthing?
What is the exact differences between HART,FOUNDATION FIELDBUS,PROFIBUS?
Can please tell mi about SIOS, PRM, SERVER, and what is the diference between PIN LAN, PCS LAN,APC Server, and please send the Doc if possible for referance,mail id patil_amit17@yahoo.com