iam interesting to design the control panel for 3 phase
pump motors by controling single phase switches.iam plan to
use fuse,contactor & relay for motor protection .how can i
select the voltage & amps rating for fuse,contactor & relay
plz guide me .if anybody clarify my doubt means it will
more helpful for my future .
Answer Posted / kuldeep singh
Fuse should be 2.0-2.5 times of full load current,
Contactor shall be 2.o times of fullload cureent ( with
AC23 duty) ,relay should be such that full load current of
motors is in mid the range of relay settings,
Isolater rating shall be 2.5 times of full load current
use 4 Amp fuse for your control circuit and aux contactor
of 2no + 2 nc contact etc
for more ask
kuldeepuee@rediffmail.com
KULDEEP SINGH
B.TECH
IITR
| Is This Answer Correct ? | 0 Yes | 1 No |
Post New Answer View All Answers
What are different types of control systems?
Rules and standards of electrical control wiring ?
how to calculation increase capacitor,increase power factor for three phase.
which book to refer in electrical engineering for iocl exam & which book for general english.
please suggest some good universities with low cost iam in totally full confusion so please help me my profile gre 283 and ielts 5.5
what is the calculation formula for motor starting torque,running torque, running torque.
Differentiate between magnetic field and magnetic flux?
What difference between ref protection and differential protection ?
what is the working process of over & under voltage relay.
our factory is going under construction mean time transformer 1000 kva 2 nos &load break swithch 12 kv & 4 nos 750 kva 2 nos & 380 kva 2 nos generator to be errcted.how to arrange earth pits &how to earth connect & neutral pit how to calculate in earth bit size.
Why in power plant projects we see DOL starting method used for motors upto 160 kW instead of star delta method
What was your role in the silicon evaluation/product ramp? What tools did you use?
In a large office how do we calculate required number of light fittings, assuming fittings are 4x18W or 2x36W fluorescent fitting ?
Please, if 1kw is equal to 1.25kva; how then do I know how many kva in 7.5kw?
design of IGBT firing circuit for 11KV