Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

A motor works on 30kw.it is working on 440volts.How much
amper will be Required?

Answer Posted / dinesh raj

Voltage =440 V
Power Facter (cos@) = 0.8
Power P = 30kW = 30000W
Formula for 3phase power P = sqr(3)*V*I*cos@
So Current I = P/sqr(3)*V*cos@

I = 30000/1.732*440*0.8
So Required amper = 49.2 A

Is This Answer Correct ?    6 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

How to select a transformer group to connect a 0,433 KV generation with 33 KV grid in bi directional flow of current

1496


Usually in the L & T make MCC feeders' power circuit,we have BMR after the MAIN CONTACTOR.,can we interchange their position, keeping the control logic same???

2054


what is the safe meggar values for motor, transformer HT, LT and Cables? IF we want to replace I/C bay at our 220 kv substation which is of 140 mw load capacity bay to be replaced by 400 mw capacity bay.other than CT(1200/1) what are the other equipment i have to replace. why we generally use 3.5 core cable or in other word 1/2 core for neutral and also confirm me that in balance conditiob(3 phase)current in neutral will zero

2211


L.A. (Lightening Arrester) is located at a place from where transmission line enters the transmitting substation. So L.A. (Lightening Arrester) is the first equipments which has to encounter with lightening, high voltage surges and switching surges. It has to absorb energy of lightening, high voltage surges, and switching surges. L.A. (Lightening Arrester) is made up of layers of semiconductors. If these layers can not tolerate energy released by lightening, high voltage surges, and switching surges the L.A. (Lightening Arrester) blasts.

1038


1. If 8.35%Z means the percentage impedance of 132kV-line from power company, we will like to reconfirm its base capacity.

1937


Pl.brief me about Electrical power distribution system from Main generating station to Industry.What is the use of in between station.

2027


Why control of DC motor is simpler?

2376


why single phase to grd test in HV cable?why not 2 phase at a time?

2223


i completed my DEEE. and i want to electrical c license. how to get it..?

2101


what is the need to express current and voltage in rms value? rms value is also called as effective value,what is effective value?

1898


what is the difference between gas group b and gas group c electrical equipment construction wise?

1810


How to see the inductance in a transmission lines

2085


how to select the no. of brushes in a lap winding?

2134


Anybody know how schematic diagram for reverse power relay? RPR for generator protection

2078


how withstand of hi-pot test outputs of transformer wire 2.5mm

1910