Answer Posted / mervin
A CT used for Instrumentation is required to be accurate
over a normal working range , whereas CT for protection is
required to five a correct CT ratio several times the rated
current . Cores made using Nicel-Iron alloy gives accuracy
upto 5 times the rated current n suitable for
Instrumentation . Cores made using Cold rolled silicon
steel are accurate upto 15 times the rated current and
suitable for protection .An accuracy of about 2-3% is
desirable for distance and differential relays .CT burden
and CT linearity should also be considered during selection
of a CT .
| Is This Answer Correct ? | 3 Yes | 0 No |
Post New Answer View All Answers
Types of test in Switchgears, MCC, NGR and DB's how it should be procced. Can anyone give me the details here or email me to pasuvaraj.k@gmail.com
why current is constant on d.c?
can i use 2000/5A Clamp meter to measure HT cable
there is an alternator 480 k.w, 400v,50hz, 4-wire running on load having leakage alternator body earthed current 38 A. is it within acceptable limit? if yes then give reference if no then how to bring within specified limit
why and how current drawn by battery charger depends upon the altitude where it is located?
What is purpose of reactor?.What is different between line and bus reactor?
How to megger test 11 kV cable and the acceptance IR value
Write down the name of 2 lady Bir Pratin of Bangladesh
Explain how you intend to work under pressure to meet up with deadline target?
Why you are switching off arc protection mcb when you are taking shutdown for lv board.
what is the acceptable limit value for Desolve Gas Analysis/
PAC and simple Ac different
what is earthing transformer? draw the winding dia.of earthing transformer.
Write down the design procedure of commutaj.
ELECTRICAL ENGINEER TEST IN FEWA ANY ONE HAVE KNOWLEDGE ABOUT THIS?????????