How to convert farad to kvar.
both are the unit of capacitor.
Answer Posted / dan
var = reactive power, microfarad = capacitance
var = reactive current x voltage = (V/Xc) x V
var = V² x 2ЛfC
Where f = frequency (Hz)
C = Capacitance (μF)
Xc = capacitive reactance = 1/(2ЛfC)
| Is This Answer Correct ? | 20 Yes | 2 No |
Post New Answer View All Answers
What is resolution of a measurement?
How to do bus bar short circuit calculation for 230KV/11kv, 60 MVA Substation?
What is the main cause of magnetism?
what is the power factor used by the PHCN in nigeria? 2. what is the difference between an alternator and generator. 3. Generation of poweris in KV but how is transmission is in MW. 4.If the transmission of power is 20,000MW how can it be increaesed to 80,000MW
at work i have a genertor/alternater what is the easyest way to work out if it is dc or ac?
What is the effect on power factor, shown by a trivector meter; incase of reverse phase sequence. If the power factor of a system is lag what meter will show in case of reverse phase sequence connected to the meter. and What in case of lead.
I'm generating a pulse of 3V with frequency 80Hz (12.5ms time period) and pulse duration 0.125ms and feeding it to a transformer since i want the pulse to get amplified around 60V. At the output amplification s happening but the pulse is changed to a spike, can you tell me what could be the reason? (an ordinary transformer 220V-12V stepdown transformer is reverse connected ie. now it is 12V-220V stepup and voltage amplification happens)
Iwould like to know barc interview questions
Starting current of a 10 HP induction Motor is ______ time’s full load current.
If not into production, how far did you follow the design and why did not you see it into production?
What is the most essential condition for the voltage build up for a d.c. Shunt generator?
I need the list of Universities who have summer intake for BS degree in Electrical Engineering.?
What is effect of over voltage and under voltage on ACB
what are the reasons of CT circuit faulty in busbar protection scheme?
What is Meter MF if External CT Ratio is 150/1 , PT Ratio is 132/110 Meter CT Ratio is 200/1 & Meter PT Ratio is 110/1