TO operate transformers in parallel, vector symbol of the
both should be same.If one transformer name plate is not
there, how can we conclude that whether the transformer is
having the same vector symbol or not?
Answer Posted / guru
Check the vector group by carrying out VECTOR Group testing
( By Injecting a 3 Ph 440v or 230 V to the primary windings
and check the voltage between the terminals in secondary
side)
For each vector group there are standard values which has
to come in the secondary side
| Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
howmany electrician should maintain for a 1000 kva used plant... in kerala..
Can anyone explain me about the capacitor calculation
Dear all i want to know SEWA Electrical Supervisor Licence test Previous Year Questions ? If any body know please send to me zohairaukllah@yahoo.com
what is feed back and what are feed back amplifiers?
Why colled 440V to 3-phase supply.
what will happen if ac and dc supplies given
Can we test the alignment of End shield and stator of turbogenerator without rotor insertion? Also how to fix maintain the alignment at site installation?
what is Insulation monitoring device. where it is used? (in switchgear room or control panel or in field equipment)
Is it possible to make a 5P10/ CT Ratio 50/1A Burden 5VA
why would amp draw on neutral wire be as much as amp draw on the hot leg.
Can i replace Earth leakage relay to the faulty Earth Faulty Relay
What is Surge Capacitor? Why it is require in Generator Circuit Breaker,inspite of surge arrester?
in indoor type circuit breakers why only the corner breaker trips specially during cold season. What is the reason.
what is the purpose of silicon dropper used in battery charger?
what is the difference b/w UHVDC and HVDC(LIGHT)?