Answer Posted / sunil kumar sinha
If the excitation of generator is lost, it will continue to
generate power by taking excitation from grid. The flux
will pass through the surface of rotor which will cause
excessive heating of rotor. Further, around moon slots the
current will jump and may cause over heating around moon
slots of generator rotor beyond limits.
There is possibility of insulation failure of rotor winding
if operated for longer period at higher load, hence loss of
excitation relay is a must protection for generator. This
relay is further monitered by excitation supervision relay
in many of sets.
| Is This Answer Correct ? | 8 Yes | 0 No |
Post New Answer View All Answers
Can we use a absolute encoder to show rpm of a motor ? what about the condition when power is off ? what is difference if a incremental one is used ?abanirout@gmail.com
(1)WHAT HAPPENS WHEN SUDDENLY LOAD GIVEN TO THE INDUCTION MOTOR ? (2)CAN WE MAKE WOOD AS MAGNET ? (3)WHAT IS THE VALUE OF MAGNETIC FLUX DENSITY IN TRANSFORMER ? (4)WHY WE ARE USING ELECTROMAGNETI NOT ELECTROSTATIC IN MACHINE ?
Why do power lines not short out when they fall into water?
A cylindrical wire is compressed in length by 10%. The percentage decrease in the resistance will be?????
can u describe the method used for protection of transmission line.
If 24 KVA AVR having Input voltage 200-400v, Output voltage 415+-1%, what will be the voltage if Load is 13A.
Can 33kva/415v transformer be run underground? If the answer is yes why and if the answer is no why?
how to calculate the lightning arrester conductor @ no of earth pits required
how do prepare ongc exam.how is it question model.i am electrical. which part covering in electrical.tell me
WHAT IS DOL STARTER? HOW IT WORK? GIVE ITS CONTROL AND POWER DIAGRAM .
Any one who apply for Ferro Scrap Nigam Limited cn join with me at rajuhalder@indiatimes.com or 09669717028
ASTM D 3455 - Standard Test Methods for Compatibility of Construction Material with Electrical Insulating Oil of Petroleum Origin has been used for Testing Transformer Oils with a product placed in it. Aged Control Oil has a Power Factor of 0.032% at 100°C. Aged Oil with a Test component has a Power Factor of 0.093% at 100°. Is this increase acceptable? If not why? How much increase is acceptable?
I am abt to give IOCL intrv.Plz sir guide me for IOCL intrvw (Electrical).Which subject to be consider. questions are generally asked from which subject.Plz help me out.
What is the name of the winding from which the supply is taken for load connections?
What is the function of interposing current transformer?