what are the standards used for earthing instruments in the
field?
Answer Posted / sam
The internal screen is always floating at the instrument.
This means we just put some heat shrink on it to seal it and
then tie it off inside the instrument and just let it lie
there. The overall screen (braiding surrounding the cable
just below the pvc outside)will be in contact with the gland
once you have installed the gland. On the gland thread you
install a copper gland ring and a red IP washer, and the
gland then are attached to the instrument. From the gland
ring you use a six mm bolt and nut with copper washers to
attached a small diameter earth wire (about 4 to 6mm is
fine). This earth wire is then attached to the outside of
the instrument at the earth connection point on it's
housing. Every instrument will have this earth connector on
the outside of it's housing. From there you attached another
earth wire to the earth boss nearby. This boss is normally
just a piece of round bar about 40mm in diameter and about
30mm long and tapped in the middle that is welded to the
structure close by, specially for this earthing of the
instruments. Again it is better to use copper washers. If no
boss is available you can use some other point on the
structure as well like a stainless steel cable tray for
instance but the earth boss should really be part of the design.
On the other side of the instrument cable at the RTU the
internal screen in attached the instrumentation clean earth.
The dirty earth is used only for electrical equipment.
Good luck
| Is This Answer Correct ? | 3 Yes | 0 No |
Post New Answer View All Answers
how we are selecting instuments by differentiating certain instruments in 4 to 20 ma range and certain in 1 to 5 v dc
A DP transmitter is used to measure the level of an open tank. The drain line of the tank is connected to a control valve, and is configured as, if the level of the tank is 90% the valve should get open 10%. And if the tank level is 10%, the valve should get open 90%. Draw wiring diagram and explain how to configure DP transmitter and control valve using HART communicator. If the span error at output is 1%, what will be the %opening of the control valve at 60% level of the tank?
What is the working principle of the magnetic meter?
Please asked me How calculate DCS controller memory.
Why not come out analog output in ABB EL3020 when display show correct value
Type of level transmitter commnly used in Procees area are the following. a.________________This type of level transmitter works as follows
can anyone tell me about the basic concepts to consider before to start a PLC panel wiring
Explain the working of an electronic level troll.
In Safe Guarding test what means by "Failed to Danger" ?
What is the difference between conductive lined pipe and conductive unlined pipe? Why do we see that?
why we use the ac supply load cell>?can we use the dc supply load cell?advantages and disadvantage of the ac supply load cell?
Where is wet leg is used?
which type inter lock use in petrochemical refinery,and oil & gas?
how do calibrate the valves.. with clear manual
What is PDS and PDMS ?