how to select a breaker (MCB,MCCB,ELCB) for 18.5 kw, 3 ph.
480 v, 60 hz induction motor?
Answer Posted / jayaraj
P=Sq rt 3VI pf
So I = 27.8 Amps. considering the staring current twice as full load current = 55A so 63 A MCCB required. Depends on the KA of the system 25KA or 50 KA MCCB can be selected.
| Is This Answer Correct ? | 13 Yes | 17 No |
Post New Answer View All Answers
what is doid
What is the temperature PROFILE OF A FLUID W. R. T. Distance from a sphere to which it is IN CONTACT which is at constant temp.?
What is meant by short-pitched winding?
what does vector group Dyn11 tell us? also tell me how will u differentiate between phase lead and phase lag thru this vector group
What is method of calculating the fault current for a MDB, 50KW, 3PH, 415V, 50HZ?
why we use sinosidal voltage / current instead of others in system?
How to calculate total harmonic distortion level(THD) in VFD? and how can we reduce harmonics?
An ELHNC 80amp 240v 30mA RCD is tripping periodically, every 30 - 180 seconds is it safe to disconnect the protection circuit?
i have install 750 kva distribution transformer at my site and want to do neutral earthing. what calculations should i follow to determine earthing conductor material and size?
What is difference between SMC supportg and Glass Fibre Reinforced Plastic Support.
What is the theoretical reason for the size of a zig zag grounding transformer to be 1.732 times less than that of a wye-delta grounding transformer used for the same application?
please send me latest & previous years question papers for IOCL Technical level questions
pls tel me the electric train traction motors name plate details like rpm,torue,voltage,amps,watts..ect..
our factory is going under construction mean time transformer 1000 kva 2 nos &load break swithch 12 kv & 4 nos 750 kva 2 nos & 380 kva 2 nos generator to be errcted.how to arrange earth pits &how to earth connect & neutral pit how to calculate in earth bit size.
Can we use 230VAC, 63A MCB for 120VAC, 63A supplied heaters load?