Answer Posted / sanjay singh artemis health i
Mr Ram
its depend on voltage & system is single or 3 phase
but i am giving example for 3 phase 415 V
P= 1.732xVxIxcosQ for 3 phase
so first we need change the KVA to KW
1kva = 1x.8(pf)
=.8kw or .8x1000 Watt
I am giving example .
considering,
V=415VOLTS
3-PHASE
P.F=08
P=1.732xVxIxCOSQ
I=.8x1000/1.732*415*08
I=1.39amps
ok
| Is This Answer Correct ? | 142 Yes | 16 No |
Post New Answer View All Answers
Why GRR starts from 60% of motor speed why not less than 60%?
The slip during plugging operation is given by= A 1-s B 2+s C 1+s D 2-s
what type of earthing do for dry fissure rock?
What is ignition module of a CAT Gas Genset G-3508 Engine, Alternator SR4B Series. HOw its checked for correct functioning.Is it repiarable or replacable?
If the earth is a good conductor of electricity, why don't people get shocked every time they walking on earth?
upto how much low RPM we will run the commercial motor which is run through VFD without any problem occurs in motor.Motor rating Duty is S1 & RPM is 1400.
Why do we need interlocking in a HT metering or Ring main unit switchgear?
can you please send me the technical questions and aptitude questions of honeywell and jindal steel electrical engg. question paper my e-mail ID is(kkesavanraj@gmail.com)
How LT megger works ?
Can anybody tell abt concrete encased earthing or grounding?
I am using submission of two ct in one and half scheme for 67/67N protection. Both CTs star point is grounded separately near ct box.Will two point ground give wrong tripping to 67/67N during fault or no matter.
I want to know Electrical Circuit?
Why MCCB is Getting tripped sometimes when there is no load in the Midnight ?
Give some differences between open loop and closed loop control systems.
what are the differences between 'exhaust fan', 'heavy-duty exhaust fan' & 'super heavy duty exhaust fan'. what are their power ratings ?