Answer Posted / virendra joshi
Dear friend ,
Transformer is a heart of the electrical system & that is
the reason it required more care.
Daily :-
Check the Oil level in Conservator.
check for any leakage in transformer
Check for any abnormal sound
check for Colour of silica gel.
Check for any air in Bucholz realay , if found realease
with the air vent provided in the relay.
Yearly.
Check the Dielectrica strengh of oil , filter it & if
required replace it.
Check the earthing value of a Earthpit if required topup
with salt & water.
Check the tighness of the connection both the way Primaty
side & secondary side.
Clean the transformer yard throughly.
If required lay the granuals in the transformer yard.
By proper shut down manually check the tripping point of HT
breaker tripping set points like ( OT, WT & Bucholz Relay )
check the secondary side voltage as per desired voltage &
if any missallign found adjust with the tap changer.
please revert if any quarry exists.
| Is This Answer Correct ? | 3 Yes | 0 No |
Post New Answer View All Answers
can some one clearly explain why -48 volt DC use in telecom site????
According to conduit size which size wiring & how many wires can we provide wires in conduit & how can we select conduit size accordingly?
during installation time of transformer and alternator which points we have to observed?
What is the difference between PS & metering CT (5p20,0.5 etc.)? Why in PS class CT only Vk is given ? Is PS class CT is more accurate than metering CT?
what is the isolation transformer. what is the isolator?
what is the use of permanent magnet generator in exciter
Can you explain about pole discrepancy scheme
in cvt,there are two windings,1a,1n and 2a,2n.in my one project i use only one winding i.e.1a,1n. the other winding is not in use, so i connect it in open delta and want to close it by ibsertibg thermal resistor. the output of cvt is 132kv/115/sqrt3. plesae tell me exact value of resistor, so i may close it to avoid the resonance phenomenin. send me answer on this email adress please. aetcon-po@aetcon.com
why h parameter are called as hybrid parameter?
What is the kiosk parts, about them and their functions ? If anybody have some PDFs files or details about this plz send it on tawhidfaisal@Yahoo.com
What is the rating of circuit breaker needed for 300 KVA load in 33 KV supply line in a transformer of 33 KV / 415 Volt ?
What is routh hurwitz stability criterion?
where can i get vijaya electricals limited in hyderabad interview auestions can u give me the website address plz
What is Auto Mains Failure Panel & Auto Synchronizing Panel
oltc of a transformer, how it works? and what are the equipment consist of describe briefly?