i heard that power factor(PF) is the main concern for
industries, if they are maintaining PF around 0.6 they will
be fined for that. now the question is, how can they improve
the PF ranging between 0.9 to 0.95 which is safe for them
i,e escaping from the fine?
Answer Posted / edy
Let say the load 500kw and u wanna increase ur power factor
from 0.6 to 0.95
500 (Tan 1-Tan 2)-u can use complex calculator to convert
from cos to tan
500 (1.33-0.32)
505kvar
u can set it with 6 step
505/6
84kvar and make it 80kvar each step
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
How is operate breaker failure scheme in substation
I need to connect a synchronous generator to the grid using automatic synchronization and two circuit breakers (one for synchronization, one for end connection to the grid), how to determinate the required diameter of the cables?
pls tell us AC plant are how do work and parts name with picture
I am an American living in Vietnam and I have recently gotten a refrigerator from Japan and it is rated for 100 vac, but the power here is 220 so I bought a voltage stabilizer it has a 1 kva output rating. Can you please tell me what the amperage is? I'm confused and without a working fridge.
How can I calculate the Mega watts required to run a plant having many electric motors and other electrical components.
DG SET BLOCK DIGRAM
We have two APFC panels in same station. I need how to connect CT in two APFC panels.can we take one CT in series connection or two separate CTs.
why i can not use thimble on capacitor duty contactor
why moisture formation found in XLPE Armoured cable outer sheath
specify the inbuilt protections in DG
I AM GOING TO ATTEND APTRANSCO ON 26TH OCT 08.PLEASE SEND ME ANY MATERIAL OR TYPE OF QUESTIONS OR EXP QUESTIONS.
how can we phase identification in a distribution line,how we recognise that which phase is coming for a house hold connection.help me............
What is signal flow graph?
What is the formula to find out two phase active & reactive power
Can you explain about Restricited earth fault protection scheme