Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

i heard that power factor(PF) is the main concern for
industries, if they are maintaining PF around 0.6 they will
be fined for that. now the question is, how can they improve
the PF ranging between 0.9 to 0.95 which is safe for them
i,e escaping from the fine?

Answer Posted / edy

Let say the load 500kw and u wanna increase ur power factor
from 0.6 to 0.95

500 (Tan 1-Tan 2)-u can use complex calculator to convert
from cos to tan
500 (1.33-0.32)
505kvar

u can set it with 6 step
505/6
84kvar and make it 80kvar each step

Is This Answer Correct ?    0 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

advantages & disadvantages of Lagging and leading power factor .

9669


What happens to voltage when current through the inductor is constant?

1196


a 100mva,400/200v transformer has leakage impdce of 10% draws a steady state line currentof---------------

1982


How to prepare electrical preventive maintenance plan & shedule of machine tools in manufacturing unit.

2231


what is meant by surge? what we called for high currents?

2118


How to calculate the phase to phase clearness of HT /// LT bus bar?????

2136


1- What is the Polarization Index number be good for 15KV 3c#500MCM electrical cable? 2- Can I use the IEEE Std 43-2000 to perfom the PI test? Thanks

3428


Why need 3phase machine double earthing?

1829


How to perform a DC resistance test In Alternator and their proceduces?

1840


any earth foult trip the relay but in welding time not trip by earth foult

3219


How to Calculate Transformer Earthing Electrode Rod Size both Body and neutral Earthing ? Any Standard Formula? Please Suggted

1677


how to measure the current by compact digital equipment with dislay which fit inside any equipment

2050


In single phase ac ups supply when current is measured with tong tester neutral current is found more than phase current.What is the reason?

2171


what is the physical connection of a analog i/p to a analog i/p module (ab plc)and through a analog o/p module(ab plc) to a analog o/p . and how all the process control by scada

1974


Why dry type cast resin transformers tap link blast in HV side while power shut down times on load?

2397