Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

Can a transformer designed for a particular voltage and
frequency rating be used for different set of mentioned
ratings? Assume that the winding does not get burnt because
of overheating at higher voltage.
If yes, then under which constraint it is possible?

Answer Posted / iamdon

Yes.

A transformer designed for a particular voltage and
frequency rating can be used for different set of
mentioned ratings as long as ratio of voltage to the
frequency does not deviates from designed value.
By emposing this constraint, the core of the transformer
will not saturate.Since the winding is assumed capable of
sustaining overheat, so only deciding factor is V/f ratio.

i.e,(V/f)=fixed at rated value.
50 Hz at 500V
25 Hz at 250V
75 Hz at 750V and so on.

Author:arbelectbit@yahoo.com

Is This Answer Correct ?    8 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Sir 33kva 2 transformer load 900 amp calc 1800 amp mana jayega

1834


What is the maximum operating temperature for a thermoplastic insulated cable?

1127


WHat is the general checks required for Dry type transformers

2085


What is the physical significant of power factor?

1925


In cable sizing calculation (determining the max route length of cable) why we choose the shortest length between cable length of full load current Iflc & starting current Istart?

3318


HOW THE OLTC TRANSFORMER SAVE ENERGY IN COMPARISON TO OFF LINE TRANSFORMER AND IS IT ECONOMICAL TO REPLACE THE OFF LINE TRANSFORMER TO OLTC TRANSFORMER

2198


in power generator normaly voltagr betwween esth to neutral is 0 but my work place generator show the volatge is 60v any body know why? thanks

1904


What is the loss of power of transformer 220kv/33kv,63/80mva of % imp12.05 at 80%load

1838


As i want some model question paper in basic computer science and history please send me immediately sir

1883


how to select the automotive wire size by mathematical calculation. for xenon headlamp with ballast. the ballast given data voltage 10-17v,current permenant 6amp, run up phase is 15amp, peak at swicth on max 400micro sec is 40amp.the sum of cable resistance is 150mohm.please provide referenc document if any for relating the peak at switch on current,time & wire wire size

2375


is there any current and voltage drop on liquid resistance starter water/soda tank ?

1988


how to CHECK CT AND PT AT THE FAULT OCCUR IN GENERATOR RELAY PANEL .

2282


what happen if generator of micro hydro running at only a small percentage of its capacity, as a comparison, if the diesel generator that runs on only a fraction of its capacity there will be a wet stacking

1944


what should be the no load current for 3 phase ac motors ranging from 5 kw to 1000kw?

1798


what is the calculation method to design core and winding of a 200kva 3phase distribution transformer?

2398