How to calculate HT XLPE CABLE for 11 kv / 433 v , 1500 kva
oil type transformer system?
plz provide step by step calculation
Answer Posted / s.srinivasan
Generally HT cable sizing is not done based on the full
load current of the equipment but based on the prospective
fault level. For a 11kV network, generally it shall not be
less than 150sqmm XLPE.
Fault level at 11kV(furnished by respective EB)=100 MVA(say)
Details on EB's fault level can be obtained from EB.
Therefore fault current= 100*1000/(SQRT(3)*11000)
= 5.25 kA
Short circuit current rating (for 3-sec duration)of HT 11kV
XLPE cables with Alu conductor is as below:
95 sqmm: 5.16 kA
120 sqmm: 6.51 kA
150 sqmm: 8.14 kA
| Is This Answer Correct ? | 139 Yes | 29 No |
Post New Answer View All Answers
I want to know Electrical Circuit?
If a surge divertor is required to be protected by 32 amp C Curve Circuit breaker does this limit the amount of protection from surges that you will acheive
How will you justify IR value and Charging voltage of any motor,transformer and Cables.......???? . . . . . . . . Plz tell me any body Baljeet Singh, engineer_89@refiff.com
Why computer humming sound occurred in ht transmission line?
why magnetising curve not start with zero voltage?
What Maximam Gap Taibaar & Bush
working principle of oil startar
which model T or pie model is prefarable in power syatem
How u can give the overload setting to any motor protection relay for a HT motors with formula and Example?
show the single line diagram of star delta starter with single phase preventer
How will polarity test of Dy5 Transformer ?
What is the rate of WCT on the Electrical Contracts comprising of DG Sets and Civil Works in Delhi ?
How much weight an electrical engine can pull??
I am doing apprenticeship training at HT switch yard in NLC. How can i get electrical c license. ??? What r the rules for getting it as an apprentice? ??
what happen when we add mentos in cold drink?& why?