How to calculate HT XLPE CABLE for 11 kv / 433 v , 1500 kva
oil type transformer system?
plz provide step by step calculation
Answer Posted / s.srinivasan
Generally HT cable sizing is not done based on the full
load current of the equipment but based on the prospective
fault level. For a 11kV network, generally it shall not be
less than 150sqmm XLPE.
Fault level at 11kV(furnished by respective EB)=100 MVA(say)
Details on EB's fault level can be obtained from EB.
Therefore fault current= 100*1000/(SQRT(3)*11000)
= 5.25 kA
Short circuit current rating (for 3-sec duration)of HT 11kV
XLPE cables with Alu conductor is as below:
95 sqmm: 5.16 kA
120 sqmm: 6.51 kA
150 sqmm: 8.14 kA
| Is This Answer Correct ? | 139 Yes | 29 No |
Post New Answer View All Answers
A ii kv 1200 A Breaker combination fixed in a cubicle. How many ampere Fuse is required? If fuse is not using, Why?
upto how many load can v connect to stabilizer which is used for tv
3 phase induction motor connection star or delta while using ac drive motor is .75 to 5.5 kw
what r PID controllers?why they r used?what is there purpose?plz Explain in detail
along with technical test papers
why surge protectetor work explain with the help of circut diagram?
how can i apilly for electrical c licencese.sir,i completed B.Tech in electrical & electronics engineering in 201onot working any company
Explain and give examples about VCB?
can we use CBCT in neutral of solidly grounded transformer? in place of three phases we can pass only one phase which decreases the size of CBCT?
how is the magnetic current test is different in delta-star and delta delta transformer.
WHAT IS THE FAULT WHEN 100HP TURBINE MOTOR TRIPS, LIST THE FAULTS AND ITS TRABULESHOOTING TIPS.. MY AUTO TARNSFORMER STARTER TRIPS
plz send me the procedure and syllabus for mseb exam
How u can give the overload setting to any motor protection relay for a HT motors with formula and Example?
What are the special cables required for explosion proof wiring?
what is the principle of operation of tungstun bulb ??