Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

Electrical Design specifications

Answer Posted / me

Greetings all,

iam working in an out door lighting design for our plant
and i calculated the total watt needed (sum of all lights)
= 53 kw, 220 volt

our power supply is 480V

so, I chosed a 75 KVA transformer dry type 480/220-127 V 3
phase 60 Hz

cable size from feeder to transformer primary = 50 mm2 (1/0
AWG)

cable size from transformer secondary to distribution panel
board = 125 mm2 (250 MCM)

distribution panel board main breacker = 250 A

So, are my calculations ok ? any changes or suggestions ?

thanks in advance

Is This Answer Correct ?    2 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Metal covered multiconductor cables shall employ a marker tape located within the cable running for its complete length in lieu of cable surface marking. Is it true or false?

2276


can anybody send the rrb chennai &rrb bopal question papers of 2006&2007.My exam is on 12 oct 2008.Its urgent

2051


how ct burden,magnetising current,ratio and knee point voltage are related & derived

2207


What is the distance between each insulator in 33kv transformer and how can it calculate

2195


WHAT SHOULD BE THE BEST CURRENT RATINGS (PRIMARY / SECONDARY)FOR A CT INSTALLED AT THE INCOMING 11KV PANE? WILL IT BE CALCULATED ON THE BASES OF MAXIMUM DEMANT VALUE OR ON SUM OF ALL TRANSFORMER'S KVA? NOMALLY MAX DEMAND REPRESENT THE MAXIMUM OPERATING LOAD OF THE PLANT AND TOTAL KVA OF (SAY 5 NUMBERS TRANSFORMERS) REPRESENT THE CONNECTED LOAD. WHICH i.e. MAX DEMAND KVA OR CONNECTED KVA ARE BETTER TO USE FOR CT CURRENT CALCULATION? PLEASE ANSWER.

1928


How to set a Zone 1 distance relay for distribution feeder?

2033


Tell me all plants load factors i.e which plant operating on which load?

2108


For a stable system, where should the poles of a system be in a root loci plot?

1237


If any one's require of phoenix contact like( relay , termilnal block , surge protection device ) , product please contect me 09878206357 chetan verma

2113


how generator load test is conducted?what are the steps?

1610


Why using synchronising methed in DG's sets?

2221


why the field winding in dc motor is not short circuited eventhough dc supply is applied across the winding

1847


How to megger test 11 kV cable and the acceptance IR value

2990


how to find the capacitance value of the motor while running??

1939


What will be the voltage impact on secondary side of two transformers with different vector groups when both voltages are compared.

2012