Answer Posted / me
Greetings all,
iam working in an out door lighting design for our plant
and i calculated the total watt needed (sum of all lights)
= 53 kw, 220 volt
our power supply is 480V
so, I chosed a 75 KVA transformer dry type 480/220-127 V 3
phase 60 Hz
cable size from feeder to transformer primary = 50 mm2 (1/0
AWG)
cable size from transformer secondary to distribution panel
board = 125 mm2 (250 MCM)
distribution panel board main breacker = 250 A
So, are my calculations ok ? any changes or suggestions ?
thanks in advance
| Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
Metal covered multiconductor cables shall employ a marker tape located within the cable running for its complete length in lieu of cable surface marking. Is it true or false?
can anybody send the rrb chennai &rrb bopal question papers of 2006&2007.My exam is on 12 oct 2008.Its urgent
how ct burden,magnetising current,ratio and knee point voltage are related & derived
What is the distance between each insulator in 33kv transformer and how can it calculate
WHAT SHOULD BE THE BEST CURRENT RATINGS (PRIMARY / SECONDARY)FOR A CT INSTALLED AT THE INCOMING 11KV PANE? WILL IT BE CALCULATED ON THE BASES OF MAXIMUM DEMANT VALUE OR ON SUM OF ALL TRANSFORMER'S KVA? NOMALLY MAX DEMAND REPRESENT THE MAXIMUM OPERATING LOAD OF THE PLANT AND TOTAL KVA OF (SAY 5 NUMBERS TRANSFORMERS) REPRESENT THE CONNECTED LOAD. WHICH i.e. MAX DEMAND KVA OR CONNECTED KVA ARE BETTER TO USE FOR CT CURRENT CALCULATION? PLEASE ANSWER.
How to set a Zone 1 distance relay for distribution feeder?
Tell me all plants load factors i.e which plant operating on which load?
For a stable system, where should the poles of a system be in a root loci plot?
If any one's require of phoenix contact like( relay , termilnal block , surge protection device ) , product please contect me 09878206357 chetan verma
how generator load test is conducted?what are the steps?
Why using synchronising methed in DG's sets?
why the field winding in dc motor is not short circuited eventhough dc supply is applied across the winding
How to megger test 11 kV cable and the acceptance IR value
how to find the capacitance value of the motor while running??
What will be the voltage impact on secondary side of two transformers with different vector groups when both voltages are compared.