WE are using a 63A MCCB(SIEMENS MAKE) for one of the feeder
in LV substation panel.It is supplying to a lighting & power
socket DB.Settings in the MCCB is Ir = 63 * 1 , Isd = 8
times of Ir , tsd = 0.5 sec( I2 t off).
Sometimes this MCCB is tripping .But no trip in DB MCB.
Can anybody tell me reason ?
From where i can know about the MCCB settings?
Answer Posted / abdul
HI Friend,
I think there must be a earth leakage in your receiving end.
Always the MCB trips for Short circit,where as the MCCB
trips for both earth leakage & short circuit.
| Is This Answer Correct ? | 1 Yes | 1 No |
Post New Answer View All Answers
why do we put a transformer on soak before loading it
stand by earth fault protection (51G) for transformer rating 2000 kVA,Dyn11,33/0.400 V. LV NCT ratio and necessary resistor and metrosil values how to calculate
how to control the speed to switched reluctance motor
-What shall be short circuit current of LV switchgear for a 1000 kva, 11.415kv, 3 phase tranformer with 5% reactance.
how to select the automotive wire size by mathematical calculation. for xenon headlamp with ballast. the ballast given data voltage 10-17v,current permenant 6amp, run up phase is 15amp, peak at swicth on max 400micro sec is 40amp.the sum of cable resistance is 150mohm.please provide referenc document if any for relating the peak at switch on current,time & wire wire size
How can claculate to attain the desired PF in the line ( HOW Much KVAR is required ) Pls Give the formula? Equate Petrochemical 0 1 how to calculate sizing of NGTR (Transformer rating,Loading resistor value and Current rating of resistor) and what is the X/R ratio. Details : 11kV,Capacitance 1.73532 micro farads,40kA for 1sec. 0 1 What will happened. if we feed 3phase supplay to the stater with out insert the rotor. How much current will flow through the stater winnding? Equate Petrochemical 0 1 What is required of exietation to the alternater. 0 1 why star point of HT motor not earthed? Equate Petrochemical 0 1 Why we are getting low voltage in star connection? Equate Petrochemical 0 2 What's ND relay & it's functions? Equate Petrochemical 0 2 How instantanious short circuit current is calculated? its formula? Equate Petrochemical 0 2 What is servo Motor? What's the advantages of this motor over Induction motor? Equate Petrochemical 0 2 What is core CT & it's function? Equate Petrochemical 0 3 what is meant by star/delta voltages as 440/220 in a 3 phase induction motor, and why it should be connected on STAR IN 3 PHASE SUPPLY L & T 0 4 What is required of exietation to the alternater. KNB 1 23 what is the design voltage for 6.6KV 2000 KVAR HT capacitor? Consultancy 0 3 Pls explain about vfd control?Where it is used, Give some example? siemens 1 22 Please explain me abt PQ diagaram in the power sector. 0 9
trasnfarmaer core make
How will you justify IR value and Charging voltage of any motor,transformer and Cables.......???? . . . . . . . . Plz tell me any body Baljeet Singh, engineer_89@refiff.com
What are the significant parts of dc generator?
State thevenin’s theorem?
what is positive , negative & zero equivalent system resistance
how to calculate slip ring induction motor stator and rotor currents??
any idea abt REVERSE METERING concept.........?
How do we arrive at selecting reactive capacitance value as 30% of h.p rating of motor?
What is different between Difnit time and instatous over current relay