132 KV TRFO BUSHING BURNT WHEN A 6.6KV HAS BEEN APPLIED
TO IT .WHY .ANY REASON ?
Answer Posted / dinesh lokhande
Let us first understand type of bushing.
Bushings for 132 kV class transformers are generally OIP
(Oil impregnated paper)bushings. However before charging
transformer air release to be done from tranformer tank and
bushings to release trapped air during oil filling. If in
any part of bushing air is trapped then air gets ionised
and provides a path for voltage beakdown resulting in
brsting of bushing due to high voltage stress in bushing.
Some other reason may be dielectric brakdown due to ageing.
Additional information.
Capacitance Tan delta test for OIP bushings can provide
readings of capacitance and tan delta which are indicative
of bushings deilectric health.
| Is This Answer Correct ? | 14 Yes | 2 No |
Post New Answer View All Answers
What is the temperature PROFILE OF A FLUID W. R. T. Distance from a sphere to which it is IN CONTACT which is at constant temp.?
what is the meaning of osr in transformer.
what is effect of leading power facter on the system and billing
what is RFCT and Insulgard Relay & It's function?
What is the main use of rotary phase converter ?
Draw the circuit of clapp oscillator?
How many types of interlocking use in screw type air compressor,make-Kaser(BSD MODEL)?
What is the formula for calculating the Instantaneous Short Circuit & overcurrent for any breaker
what is self capacitance of inductor
What is the minimum IR value of HT/ LT cable? Pls post separetely!!!!!
How to derive detailed design of Suitable bus Bar for 100A for 6.6KV?
State ohm’s law?
Determine the BTU size of an aircon for 20 sq metre room
why ct ,cvt should be stored in a vertical position?
what is mean by parallel operation of permanent magnet generators