If connected load of Asphalt plant is 375Kw. What suitable
KVA DG set is required. What is calculation formula. what
extra load have to consider. in what efficiency it will
work.
Answer Posted / munish saini
KW=KVA*PF
PF=.8
KW=375
KVA=KW/PF,=375/.8=468.75KVA
20 Percent required more as eppiciency Factor
so required dg should be=562.5 KVA
Is This Answer Correct ? | 4 Yes | 1 No |
Post New Answer View All Answers
How does an induction motor start?
Dear sir my name Ankit i m Diploma holder present working in Welspun Corp ltd Anjar as Asst.engg (salary 14400/month ctc) i Would like to change my company also i have selected in ford India pvt ltd Sanand as trainee Tech with salary 12000/month so please suggest me for changing my job hope for *ve response