Why CT secondary should not be kept open?

Answer Posted / iamdon

The CT secondary should not be left opened secondary due to
following reasons:

1)Zero current in secondary leads zero back emf.So primary
current becomes very high as the primary resistance is very
low.Large heat generated may burn the winding and core.If
the transformer sustain this heat, even then its operation
becomes improper as explained below.

2)CT is bascially a step up transformer.So high voltage
induced in secondary may saturate the core (core becomes
permanently damaged).So the operating point advances in non
linear region,which makes the transformer operation improper
(secomdary current will not replicate the primary according
to the turn ratio).

3)High voltage spikes(order of kV) produced in secondary side
may endanger the life of personnel working on the secondary
side.

4)High voltage spikes(order of kV) produced in secondary side
is sufficient to break down the transformer insulation.

Author:arbelectbit@yahoo.com

Is This Answer Correct ?    30 Yes 19 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what is basic difference betmeen normal & flame proof motor??

1649


which type of effect of turbine and generator reverse power protection ?

3764


Define delay time.

665


Q.1:What protection will be used on HT and LT side of 33/0.4 KV, MVA transformer. Indicate capacities of protective device to be used. Q.2:Which types of back-up protections are used in the power transformers? What do you understand by the term over travel in the relay? Q.3:How star and delta connected winding transformer are provided from earth fault

1710


Mention the methods for starting an induction motor?

645






how does the thyistor work in dc drive?

1556


why we used ZNO in Lightning arrester.

1543


what happen if generator of micro hydro running at only a small percentage of its capacity, as a comparison, if the diesel generator that runs on only a fraction of its capacity there will be a wet stacking

1453


Dear Sir/Madam, I have one questions we have three steam turbines and one Gas turbine and our industry linked with the public network, we have protection system one of the protection is reverse power we can export just four MW only i would like to ask about how to calculate the reverse power. Thank you in advance best regards

1646


what is diff. between earthing grid,earthing mess, earting grid?

1878


is it value of power factor is more than unit. whats effects in the source supply

1601


If Neutral Grounding Resistor (GR) failed/shorted. Is it repairable.

1157


Why the field rheostat is adjusted such that the voltmeter reads 380V

1829


why the NGR (neutral grounding resistor) always OFF during DG off?

3077


what is the use of static frequency converter and static excitation equipment? and where it is employed? for what?

3047