Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

Can the efficiency of transformer be measured with the help
of wattmeter readings taken at primary and secondary side?
Support the answer.

Answer Posted / iamdon

No,Transformer efficiency measured with the help of
wattmeter can't be reliable.

The reason is
The efiiciency of transformer is very high (order of 98.5-
99+)% due to static nature of it.The error associated with
ordinary wattmeter is in the range of 1-2 % .Under this
condition the readings taken cann't be reliable.

The efiiciency is measured with the help of data taken from
two tests namely
Open circuit test--indiaction of core loss
Short circuit test--indication of copper loss.

Author:arbelectbit@yahoo.com

Is This Answer Correct ?    2 Yes 2 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

sir vizag steel ka junior trainee ka paper kitne number ka ayega

2309


explain the mode of metal iranafer in Co,welding

1636


can we choose current transformer secondary, to calculate residual flux in a power transformer, so as its saturation is close to the saturation level of power transformer?

1557


What is inductance?

1273


What is minimum permicible value of leackage current for LT Panle when applying voltage up to 3 KV for 5 Minuits?

2304


what & how to check the lightning arrester

1968


importance of reactive power management

2081


what is the calculation method to design core and winding of a 200kva 3phase distribution transformer?

2465


What is the two pole structure?

2008


WHAT CAUSED THRESHOLD VOLTAGE TO EXIST?

4113


Dear all, I just want to ask an expert on this forum for some insights. For the magnetic balance test, when applied voltage on a Delta-Star transformer e.g. Dyn11, the following relationships apply for HV side: 1.  H1-H2 = H2-H3 H3-H1 2.  H2-H3 = H3-H1 H1-H2 3.  H3-H1 = H1-H2 H2-H3 For the LV side also: 4.  X1-X0 = X2-X0 X3-X0 5.  X2-X0 = X3-X0 X1-X0 6.  X3-X0 = X1-X0 X2-X0 Is there a similar pattern for Y-d, Y-Y, D-d? And how about Y-z, D-z, Z-y transformers? I've tested a YNzn5 transformer and for LV side I don't see the pattern. In this particular case I got for LV side the following (see values below): H1-H0  H2-H0  H3-H0    X0-X1  X0-X2  X0-X3 128.0  119.9  7.2      29.2   13.3   15.8 70.7   128.4  59.2     23.4   22.0   3.6 7.2    120.1  128.1    13.4   29.3   15.8 What is the relationship here for LV? For row 1 I see the relationship, for row 3 I also see but it's shifted, but for row 2 I don't see such relationship. Any suggestions, answers, someone?

1909


What is the general system requirement of alternator?

1898


The D.C. spark test is applicable to single conductor cable & assemblies of insulated single conductor cables without insulation shield,metallic sheath or metalic armor?

1904


dg started in plc mode and load taken later one battery terminal connection will be disconnected by loose connection what will happen for dg and shall we connect battery terminals while dg in load time?

2131


how to carry out Magnetizing Current Test on Distribution transformer and what purpose we are doing this test. why transformer rating in always in KVA ? what ispositive, negative, zero sequence impedence? How ElCB tripping if Neutral touch with ground Why AC & DC capacitor are use in UPS ? why motor rating in KW? how to syncronize two dg sets

2249