i have D.p. transmitter of range 0 to 2540 mmWC, i want to
use this for flow measurement (0 to 500 ltr/hr.) what
should i do?
Answer Posted / k.sreenivasan
Mr.PasavaRaj,
Your question misses a major point.
Do you have a flow sensor (like orifice or annubar etc)
already installed?If yes, Then you have to match the DP
required by the sensor to the transmitter DP Range.Please
note that 2540 mm wc of the transmitter range can be
changed using communicator (If it is HART) based on
transmitter specifcations.Check what is the minimum span
the tranmitter can be calibrated? if that is greater than
the sensor DP, you have to look for another transmitter.
| Is This Answer Correct ? | 5 Yes | 0 No |
Post New Answer View All Answers
Specify eight technical requirements that you would consider important, when deciding upon a particular control valve?
I need control valve ISA hand book. Is there any site to download that big book containing all the pages. Written by Paul Friedmann
What are different type of instrument cable
How hart protocol can be connected with control valves?
How process line mpm calculation is done?
why fuse block is not used for AI signal?
What is the working principle of the magnetic meter?
Q- Control problem are mainly classified in _____ types. a-)4 b-)3 c-)6 d-)nono of these Few of them i know is 1- regulator type problem (eg- Air conditioner) 2- tracking problem (eg missile trcking problem) 3- sybernatics 4- optimal control problem
In a gas over oil actuator, after the opening/closing of valve, how the gas is vented out? How does the hydraulic/gas circuit function?
How to interfacing microcontroller with a DC motor
Which are all the commonly used Bordon tubes in the pressure gauges. Do any one use ASTM A 312 tubes for this purpose?
Isometric drawings are generated during _________________ phase of a project
ORP sensor working principle?
Explain how thw analog to digital converter works with the circuit diagram
steps for installing orifice plate?