How can calculate ups battery back up time?
Answer Posted / r.gopalakrishnan
SEE SUPPOSE IF I NEED 740 WATTS USAGE BACK UP TIME UP TO 3
HOURS, THAN I CAN CALCULATE LIKE THIS(EXAMPLE 1
PC@350WATTS,3 FANS@80X3=240WATTS& 3TUBE LIGHTS
@(40+10CHOKE)=50=150WATTS)TOTAL=740 WATTS REQUIRE,= 740
DIVIDED BY 12 V=(61.666667)>61 Ah per hourx3
ours=183Ahbattery,(180Ah Battery).now you have selected
battery & than select a UPS/inverter that is you can only
get 80% of your UPS/inverter.Ex;1000 watts Ups/inverter.that
will be always safe for you & ever.thanks.R.GOPALAKRISHNAN.
| Is This Answer Correct ? | 96 Yes | 40 No |
Post New Answer View All Answers
Under wat condition statcom operates as an inductor for the transmission line?
how to enter inverter parameter? without manaual?
What is the differentional relay...what is the work of this in power Tx. how it is works..
what is proper capacitor placement? How to evaluate capacitor size?
why swinburnes test cannot be performed on series machines?explain
How capacitor improves pf
why booster transformer is used in sumpners test conducted on transformer????
Swg formulae
I am getting above 60 V as open delta voltage against single phase unit ICT at tertiary delta formed and ICT getting trippped on NDR. ICT tested and found in order. PTs provided on tertiary are tested and in order. what may be the reason?
how to calculate the conductor size for certain KV transmission line and distribution line?
difine electrical ballast in HPSVL
please send the last 5 years {{{JUNIOR ENGINEER - ELECTICAL, ELECTRONICS RRB CHENNAI and secundrabad}}} TECHNICAL question papers TO MY EMAIL ID dinesh100701@gmail.com
After taking shutdown of 11kv feeder, if you see 5kv by phasing stick in the cable side, is it possible to close earth switch in cable.
What is Surge Capacitor? Why it is use in Generator Circuit Breaker?
state basic meaning of 'INDUSTIAL AUTOMATION'?