How can calculate ups battery back up time?

Answer Posted / r.gopalakrishnan

SEE SUPPOSE IF I NEED 740 WATTS USAGE BACK UP TIME UP TO 3
HOURS, THAN I CAN CALCULATE LIKE THIS(EXAMPLE 1
PC@350WATTS,3 FANS@80X3=240WATTS& 3TUBE LIGHTS
@(40+10CHOKE)=50=150WATTS)TOTAL=740 WATTS REQUIRE,= 740
DIVIDED BY 12 V=(61.666667)>61 Ah per hourx3
ours=183Ahbattery,(180Ah Battery).now you have selected
battery & than select a UPS/inverter that is you can only
get 80% of your UPS/inverter.Ex;1000 watts Ups/inverter.that
will be always safe for you & ever.thanks.R.GOPALAKRISHNAN.

Is This Answer Correct ?    96 Yes 40 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what purpose to use excaiter in DG.?

2224


Give some differences between open loop and closed loop control systems.

673


how to find Harmonics and types as per the equipemnts

780


what can be the causes of capacitor start motor having a higher current that its actual

1514


How Can I calculate for the photometrics requirements for a street lighting? Data given are: 45 units of 6 meter light pole with 150 watts metal halide lamp, 220 volts and installed in a promenade area.

1426






how many single tension hardware are required on a double circuit transmission tower?

1484


How will change the frequency in distribution side?

1372


what things to be considered when designing UPS

1308


how choose conductor&depending upon load

1445


how external lighting design? please give examples?

1433


What is the mechanism of WTI

1381


What will happen if i used 11KV earth ht kit to 11 KV / 11 KV cable termination?

998


explain the process of commutation in a dc machine. Explain what are inter-poles and why they are required in a dc machine.

701


Does the direction of rotation of d.c. Shunt motor would get reversed if the armature current and field current both are reversed?

657


why we can stote dc? why we cant store ac?

1625