TO operate transformers in parallel, vector symbol of the
both should be same.If one transformer name plate is not
there, how can we conclude that whether the transformer is
having the same vector symbol or not?
Answer Posted / mgalalkhedr
This vector group test is done at site to check if their is
any damage in the windings during transportation and
erection.
3 -phase AC supply is given on HV side. R-Phase HV and r-
phase LV shorted.
Then to qualify the test following conditions are to be
satisfied after measurement of voltages.
nR+nY=RY, By>> Bb and Yb=Yy.
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
at work we have a 3 phase motor but on testing one phase isnt getting a reading. it runs 24 hours a day all week. stops and starts well no noise or heating. the phase isnt down to earth.is it just a bad meter reading or not? phases one and three came up with a resistance reading of 0.4 but phase 2 couldnt get anything shows up as open circuit.
what is the need of starter in tube light and what type of starter is used in that?
How to distinguish whether MCB is DC or AC looking at it physically
What is the maximum number of swithes that can be connected in series up to down stream point in an LV Distribution system?
How we can calculate the Amps for the cable Ex:- For 1sqmm wire how many amps we can draw (calculation)
In Generator How suction compression power and exhaust works ?
armature is that part in which current is induced since in dc motor we supply current to the conductor so why we call it armature?
What are PLC leader logic program method
Why the unit sizes of hydro generating machines are not standardized as in case of thermal powerplants?
Pleae send me last 5 years of Question book about RRB chennai.
Installation method of self treated earth electrode.
in single phase converter, the no.of scr's conducting during overlap a)1 b)2 c)3 d)4
why the arc welding machines require parallel earthing systems? ie why each machines are connected to earth pit by separate wires during earthing? wats it adavantages?
Can we use BS 6651 and BS EN 62305 standards for computer room lightning ptotection in substation?
Why back emf used for a dc motor? Highlight its significance.