Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

How the Transformer oil testing is done & Why oil dielectric
goes LOW & what is solution for that ??

Answer Posted / pillay

The sample oil to be tested for dielectric test is collected
and put into the tester and the average of 6 tests is
taken.The minimum withold voltage is as per local regulations.
causes of low dielectric results are usually exposure of the
insulating oil to moisture through the breather or there is an
exposed opening, poor quality oil being used. high acidic
content.The insulating oil should be replaced or dehydrated.
breathers silica gels should be maintained good all the time
and check for any leaks or any exposure to atmosphere must be
rectified.

Is This Answer Correct ?    15 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Is there any relevant technique to produce power from light and heat energy of the sun simultaneosly from same rays of light?

1881


Help need in transformer !? Hello Friends The parameters of 2300/230 v 50hz t/f is R1=0.286 ohm R`2=0.319 ohm Rc=240 ohm X1=0.73 ohm X`2=0.73 ohm Xm=49.2 ohm Secondary Load impedance ZL=0.387+J0.29 solve the exact equivalent circuit with normal voltage across primery.. I know every thing but i cant find CURRENT I1=? and I`2=? Please help me give solution or only Formula please please...

3110


How impulse levels are calculated that for 11kV impulse is 75kvp, for 24kV impulse is 125kvp ?

2004


what are the factors to be considered while design the breaker either HT or LT??

1932


Explain the operation carried out in thermal power stations?

1046


How to calculate multiplication factor in kva example 500kva ans pls ?

1961


What is main cause of cable's terminal point burned in Lug on high temperature although lug and cable selection is ok as per stantard and also tightness is ok as per situation. so please take in deep and tell correct answer thanku.

8297


what is the IS foe lightning arrester?

2172


What is the minimum IR value of HT/ LT cable? Pls post separetely!!!!!

2452


What is the slip speed?

1096


what is the basic need of domestic loads 1- voltage 2- current

2114


what is meant by poly phase induction motor ? how its operating by single phase or three phase?

2161


Is it possible to connect a safety device in to parallel?

2161


Write down the design procedure of commutaj.

2138


How does cost of generation from hydropower plant compare with other sources of electricity?

1061