Hai I have 2500KVA,Transformer,13.8KV/380.DELTA/STAR.How
much load that I can take interms of current?How can I
calculate also when I have loads in KW?

Answer Posted / saqib haroon

as per my point of view,answer of the input current is
wrong. Why the respectable brother put power factore value
with KVA rating, as per formula only once we will put PF
value, which will divide this KVA rating.

In this case the answer will be
P1= 1.73*V1*I1*cosphi
2500= 1.73*13.8*I1*0.8
2500/1.73*13.8*0.8= I1
131 A = I1

Remaining portion is OK

Is This Answer Correct ?    3 Yes 5 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

how to remover corona effect and hysteresis losses from contactor

1570


what is vA rating and class of a ct.

1428


please send previous exams question papers

1402


specify the inbuilt protections in DG

1624


i want design of D.C.MOTOR 1HP 960RPM AND 2HP 960RPM ITS URRGENT

1558






what is the range of maximum DOL and SDS can be use for pump and fan application

638


DEAR SIR/MADAM,CLEARLY EXPLAIN ABOUT CRAWLING AND COGGING EFFECTS IN INDUCTION MOTOR.

1441


what is the minimum winding resistance of 30hp compressor, to run or to switch on

1408


why Y CONNECTION IS BETTER INTERMS OF EFFICIENCY AND P.F FOR A LAOD LESS THAN 40% AND WHY AFTER DELTA IS BETTER FOR > 40%

1489


What is the type of earth fault protection used in battery? explain.

1869


If any cable burnt how can we identify it burnt by high current of high voltage? 

2009


If we have use two power cable for incomer, that time how many use cbct for earth leakage protection? 1 or 2 if 1 way? If 2 way?

1649


What is the function of attenuator in cro?

743


What is difference between SMC supportg and Glass Fibre Reinforced Plastic Support.

1865


difine electrical ballast in HPSVL

1566