Answer Posted / ramji
Mr.Sudheer u r not clear.U r telling the condition after DG
starting only, not during running.
Mr.Shri can u please explain me how the voltage will be
fluctuating if the AVR is OFF.
In parallel mode if the AVR of the suspected DG
fails, then the reactive power of the particulat DG gets
reversed because the DG will be out of its running
quadrant.Since the reactive power is reversed, DG will be
trip on under reactance.Also if it is not tripped, its
outgoing current will be increased, so it will trip on Over
current.
In island mode if the AVR of suspected DG set
fails, then the loads connected to it will be thrown off
immediatly and the DG may trip on prime mover overspeed due
to sudden throw of load or undervoltage protection on DG.
| Is This Answer Correct ? | 6 Yes | 2 No |
Post New Answer View All Answers
Can anybody tell abt concrete encased earthing or grounding?
WHATIS TIME CONSTANT? WHATIS ITS SIGNIFICANCE? ILLUSTRATE THROUGH EXAMLES.
How to check the Bushings of the transformer?
How to calculate the value of earth capacitance in a transmission line.
what is the acceptable limit value for Desolve Gas Analysis/
What happen to the transformer if the OLTC frequently used for lower and raise occured 50times daily?
In which of the following case, the rotating magnetic field is reversed? A regenerative breaking B plugging C dynamic breaking D forward motoring
what is ps impedance test
how does the rotating m.m.f is produced in the 3-phase induction motor and how the poles are created in 3-phase induction motor ?
How can maintain our H.T. motors used in cement plant. please send me procedure.
which is better to use svc or synchronous condenser why ?
Why MCCB is Getting tripped sometimes when there is no load in the Midnight ?
explain working principle of earth leakage relay
How vfd saving power.
can u describe the method used for protection of transmission line.