Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

if AVR fails in D.G set, what will be the effect?

Answer Posted / ramji

Mr.Sudheer u r not clear.U r telling the condition after DG
starting only, not during running.
Mr.Shri can u please explain me how the voltage will be
fluctuating if the AVR is OFF.

In parallel mode if the AVR of the suspected DG
fails, then the reactive power of the particulat DG gets
reversed because the DG will be out of its running
quadrant.Since the reactive power is reversed, DG will be
trip on under reactance.Also if it is not tripped, its
outgoing current will be increased, so it will trip on Over
current.

In island mode if the AVR of suspected DG set
fails, then the loads connected to it will be thrown off
immediatly and the DG may trip on prime mover overspeed due
to sudden throw of load or undervoltage protection on DG.

Is This Answer Correct ?    6 Yes 2 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What is Bolted fault?

2155


How the annunciator works ? How to do its wiring

2239


can we find the inductance of a induction motor?

1918


Why in metering Ct for ammeters ct secondary side is grounded for each Ct but not in case of CBCT (Core balance current transformer)..kindly some1 highlights the reason..is it because net flux is zero?

1369


When calculating the speed of a rotor required for a particular frequency of synchronous generator we use the equation 60f/p Is this p is the number of pole pairs of rotor & do we consider the number of pole pairs in the stator is 1?

1927


hello!my name is sheikh iam preparing for indian engineering servieces,please send me the old question papers..to sheikhshaazforjobs@gmail.com

2028


Why current shoots up in the secondary on the knee point voltage during saturation test of CT? How core saturation effects the secondary current (while the primary side is open)? What the logic behind this?

1953


On a 6 KVA UPS we have to provide a DC MCB for Battery bank of 16 nos (12 V 42 AH). What Shall be the current rating of DC MCB ?

2570


Hi Suppose we have a wye/wye transformer which is grounded at both sides,in this situation, do we have ay ground transformer? in other words, ground transformer can do any thing more (while we have nuetral wire in both sides)? As the last question, what about 3rd harmonic? we have two choices: first using wye/delta transformer + ground transformer and second using wye/wye earthed connection.in the former choice, we dont have 3rd harmoonic at the secondary side but what about Yn/yn conection? do we suffer from 3rd harmonic in the Yn/yn connection?

1911


why burdens of VTs is more than CTs?

1716


What is the meaning of Insulation H for transformers????

2089


CALCULATE THE TOTAL VOLTAGE DROP AND SELECT THE CABLE SIZE IN MM-SQARE FOR A PANEL-262KW AT 110 METER FROM THE SOURCE SUPPLY , SUPPLY VOLTAGE 240/415

2602


What is difference between mcb and mccb.

1096


xpression 'document.FrmQF.myemail' [

1949


what is the control circuit for operating the clean room air shower

2213