Answer Posted / ramji
Mr.Sudheer u r not clear.U r telling the condition after DG
starting only, not during running.
Mr.Shri can u please explain me how the voltage will be
fluctuating if the AVR is OFF.
In parallel mode if the AVR of the suspected DG
fails, then the reactive power of the particulat DG gets
reversed because the DG will be out of its running
quadrant.Since the reactive power is reversed, DG will be
trip on under reactance.Also if it is not tripped, its
outgoing current will be increased, so it will trip on Over
current.
In island mode if the AVR of suspected DG set
fails, then the loads connected to it will be thrown off
immediatly and the DG may trip on prime mover overspeed due
to sudden throw of load or undervoltage protection on DG.
| Is This Answer Correct ? | 6 Yes | 2 No |
Post New Answer View All Answers
what should be the ideal gauge of wire (In sq mm) for different loads in Ampere?
In MEP Services what are parts of STP and what are there function?
What are the types of power in electrical power?
Define cut-off rate?
how to check regenerative load in drived motor
which capacity of RCCB used for five thousand watt electricity load?
Write the force balance equation of m ideal mass element.
sir please send me previous year questions of jspl of electrical section through which i could prepare myself fpr the test.
role of europe union in UK safety legistlation (electrical safety)
What is meant by vector group
what are the difference between AC lamp and DC lamp
What is the real function of reverse power relay in generator panel while syncronising?
Why the symbol of register is "zig zag"
please anybody help me to find out the BHEL trainee Exam previous year questions papers . if u ve pls. send it to surekhared@gmail.com
Whether 3 phase induction motorwith 100 hp capacity , Amp 160 for which sensitive earth fault relay , type CTUM 15 can be used?