What is RTCC in a transfomer and specify its function.
Answer Posted / rahul kumar
In transformers Output Voltage can be controlled either by
Off Circuit Tap Changer (Manual tap changing)or By On -
Load Tap Changer-OLTC (Automatic Changing).
In the transformer with OLTC, it is a closed loop system,
with follwing components:
#1. AVR (Automatic Volatge Regulator- an electronic
programable device). With this AVR we can set the Output
Voltage of the transformers. The Output Voltage of the
transformer is fed into the AVR through the LT Panel. The
AVR Compares the SET voltage & the Output Voltage and gives
the error signal, if any, to the OLTC through the RTCC
Panel for tap changing. This AVR is mounted in the RTCC.
#2. RTCC (Remote Tap Changing Cubicle):This is a panel
consisting of the AVR, Dispaly for Tap Position, Voltage,
LEDs for Raise & Lower of Taps relays, Selector Switches
for Auto Manual Selection... In AUTO MODE the voltage is
contrlled by the AVR. I manual Mode the operator can
Increase / decrease the voltage by changing the Taps
maually through the Push Button in the RTCC.
| Is This Answer Correct ? | 35 Yes | 3 No |
Post New Answer View All Answers
whether starting current is limited to rated current of motor through soft starting or it exceeds the rated current?
Name two types of electrical analogous for mechanical system.
Why HT 11 KV Slipring Motors are connected in star ?
Difference between field rheostat and armature rheostat.
where does 22kv line starts
Brief working principle of stabilizer,application & safety precautions
What is dynamo?How it works and what is the function of dynamo in a DG.
How the PF control while running DG set with load
how to calculate earth fault relay current and CBCT ratio
In Dyn11 power transformer if any one of the 3 phases connected to earth in star connected side then please explain effect of the current flow in delta connected side of transformer.(In this case if one phase is shorted to ground in star connected side then we observe the current flow in two phases only not three phases in delta connected primary side. Please explain why it is so?)
When we use air circuit breaker, it has O/L protection ,time delay SC protection, Instataneous SC protection & ground fault protection. They all have some setting range. But what is the suitable/allowable setting for the above protection which will be safe for the equipment? For example-O/L protection setting have a range of (0.4,0.45,0.5,0.55,0.6,0.65,0.7,0.8,0.9,1.0)xIn Time delay SC protection have a range of (1.25,1.5,2,3,4,6,8,10,12)xIn Time delay setting is 0.02,0.1,0.2,0.3,0.4 Instataneous setting is fixed to 20xIn Gound fault setting is given 100A,300A,600A,900A,1200A This setting are for 2500A ACB. So what will be the basic allowable setting for the above protection? is there any formulae to calculate this<
Where voltage are high and current to be interrupted is low the breaker preferred is:
What is the percentage loss for aluminium wire for HT line more than 11KVa
can anybody sent me power grid questions. what subject should i prefer for preparation?
what is kondo syatem in eletrical traction