What types of testing in 11Kv Ht switchgeat during testing?

Answer Posted / n.venkidusamy

I think that site tests.ie. Pre commissioning Tests of
following.
1. Insulation Resistance Test for breaker and protection
and other cables
2. Check for spirit level
3. Mechanical spring charge test
4. Mechanical ON/OFF test
5. Electrical spring charge test
6. Electrica ON/OFF Both Local and remote Test
7. Contact resistance Test
8. opening and Closing timings tests.
9. Protection trip Test
10. Check for operation of Closing coil at 80% and Trip
coil at 70% rated Control D.C.voltage

Is This Answer Correct ?    14 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what is the difference between electrical and electronic choke?

1572


how to select electrical equipment such as fuse,dg,transformer,motor,msb,wire,cable as per the connecting load..please mention any books to design,take licence

2618


Can any body tell me about INNER SHUNT COMPOUND MOTOR diagram?

1757


State any two nuclear power stations in India, with their generating capacity.

1485


what is the earth current,reverse power,electrical trip generator short circuit,low voltage, high voltage please discribe me

1729






EHV current carrying parts need to have smooth finish,then how can a 245kv GIS with emery finish can run so long?

1494


Yazaki india pvt ltd interview questions qurey related

649


What will happen if the voltage in my house drops from 220V to any lower voltage?

1753


how to operate and maintenance of 1500 kva diesel generator set

1436


1. If 8.35%Z means the percentage impedance of 132kV-line from power company, we will like to reconfirm its base capacity.

1652


Can anyone explain me about the capacitor calculation

1800


Why 15Amp. MCB is suitable to carry load of 1.5Ton Ac please Explain?

1726


what is the IEC standard for Power Cable installation in onshore (like in direct buried ground or above groung)

2254


Importance of fault current in power transformers and how to monitor the same? How is it different from winding temperature?

1438


a starter used for squirrel cage induction motor?

1325