Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

I HAVE A 1 MVA TRANSFORMER, I WANT TO KNOW THE FAULT LEVEL OF
THE SYSTEM ( WHAT IS FAULT LEVEL PLEASE EXPLAIN WITH EXAMPLE)

Answer Posted / satyajit sadhu

FAULT LEVEL MEANS SHORT CIRCUIT CAPACITY OF TRANSFORMER.YOU
HAVE NOT MENTIONED THE VALUE OF TRANSFORMER RATIO & % OF
IMPEDENCE.ASSUMED VOLTAGE RATIO= 11KV/415 V & % OF
IMPEDENCE=6%.
RATED FULL LOAD AMP OUTPUT =1MVA/(415 X 1.732)=1391.25A
SO SHORT CIRCUIT CAPACITY OF TRANSFORMER= 1391.25/6%
=23187.44 A
IF ANY FAULT OCCURED THEN THE ABOVE TRANSFORMER WITHSTAND
THE SHORT CIRCUIT CURRENT OF 23187 A.

Is This Answer Correct ?    33 Yes 4 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

List the time domain specifications.

1021


why we can use 1 to 5V dc

1927


what is the basic need of domestic loads 1- voltage 2- current

2069


Transformer how to maintaince a check b check c check d check

2046


xpression 'document.FrmQF.myemail' [

1965


What is the basic rule for block diagram reduction technique?

1202


HOW TO CALCULATE AMPs OF CURRENT TRANSFORMER IN HT Panel

2335


to vary valtage from 0 - max a variac is necessary . so how to design for high power applications nearly about 200KW power

2032


What is the Designing & Selection Procedure for a DG/Transormer of rated capacity?

2143


brief notes on ammeters

1989


What is meant by impedance? difference between high & low impedance ?

2023


difference between main metering kiosk and check metering kiosk

2938


How to confirm the Phase shifting Transformer VECTOR GROUP relation , as below ZNy11.45d10.45-ZNYy0.15d11.15

3217


plz send me HPCL apptitude paper.. maulik_elect@yahoo.co.in

2043


1) Explain why we don't link the two earthing system ht and mv on a pole mounted transformer sub-station.

1759