AT THE TIME OF INSTALLING THE POWER PLANT POWER IS TAKEN
FROM NEARBY GRID AND GIVING THE SUPPLY TO THE GENERATOR
WHICH ACTS AS MOTOR. WHAT IS THE NEED OF RUNNING THE
GENERATOR AS MOTOR?
Answer Posted / s.p.p.pathirana
The perpose is connecting grid power to the power plant
generators for syncronized both the system such as
(volt,freqency,and phase sequence)generator or alternator
has coupled to the engine. according to the question that
motor will turn engine to the oposite derection and engine
may damaged. there for generator have protection system to
prevent this. its call reverse power protection. power
plant for support to the grid and have connected grid power
cable to the generators through individual there circuit
breakers. generator breaker cannot close with engine
standby mode. if this correct please try to understand.
Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
what is mppt (maximum power point tracking ) and how they used in solar power generation ??? what are the main components used in mppt?????
HOW can i REuse the fused MLL LAMPS & GLS LAMPS at our factory
how to select automotive wire by mathematical equation with given current, vlotage and resistance
What descriptive information does the NEC require to be marked on all conductors?
upto how many load can v connect to stabilizer which is used for tv
What are the Formula of computing Back up Time of 500kVA UPS with 4 Battery Banks, each bank composed of 43 pcs of Batteries 12V150Ah. How to compute the Back up Time of UPS? We have also 3X500kVA UPS running in Parallel same composition as I write above.
What is kvar?
what are the safety measures of induction motor?
how to calculate voltage drop and followed by cable calculation?is there avail in formula?
Define the three phase formula fuse.
what is the use of surge suppresser in 33 KV incoming panel. where it must be installed,inseries with incoming cable surge suppresser must be at incoming of the breaker are outgoing of the breaker
design of IGBT firing circuit for 11KV
I use 20 nos led tube 4feet, in pathway 100mtr approximate, so what size cable i use for lighting
draw 3 phase rectifier diagram
HELLO SIR, IAM PREPARING HPCL EXAMS. SO PLS SEND MATERIAL OF HPCL ELECTRICAL ENG..TO VIJAY_8888@YMAIL.COM