Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

what type of earthing is done on hilly rocks.

Answer Posted / munish sharma

In Rocky Area the soil resistivity comes out to be very
high.The overall grounging structure is based on following
criteria
1.Area Of the Switchyard
2.Surface Layer Resistivity
3.Soil Structure
4.Safety PArameters
5.Fault Current Distribution
There Are Certain Techniques in case of HIgh Soil
Resistivity as
1.Deep Groung well Earthing
2.If area is limited of the Switchyard,use Remote grid
along with main grid buried in low resistivity material
3. Soil Treatment
4. Use Grounging rods to take effect of deeoer low
resistivity layers

Is This Answer Correct ?    6 Yes 2 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Shall I use 40A semiconductor Fuses in 32 A SFU ? Frame size is same. What Happen if Fuses burn on SFU?

2121


What is vacuum circuit breaker.define with cause and where be use it device?

1313


Why let through energy not considered for ACB breaker while cable sizing?

2419


how i can calculate the size for fire cable

2022


how to calculate transformer load?

2478


Its possible to use 3core 2R of 240 sq.mm cable for 3phases & separely 50sq.mm 3core cable fully for Neutral for connection of PCC to MCC 3ph..4wire system?

2102


WHAT IS SHORT CIRCUIT STRENGTH OF 100 AMPS MCCB?

2117


what is the difference between circular wdg & ractangular wdg?

2061


Brushes are placed at magnetically neutral axis,when brushes reach that point,the armature conductor gets shorted,but it can be seen that the dc supply is also shorted,wont that get damage? help me plz

2301


Differentiate between Zero and Negative sequence current

1915


Dear all i want to know SEWA Electrical Supervisor Licence test Previous Year Questions ? If any body know please send to me zohairaukllah@yahoo.com

1038


how to select the double earth conductor if 21A full load?

2069


in HT service 3ph 4 wire service Y-phase voltage shows zero . whether it is meter fault? or what be the reason ? if y-ph voltage zero ,can current is recorded? reasons for failure?

1933


Why an ac solenoid valve attract the plunger even though we interchanges the terminal? Will the poles changes?

1221


please send the IS strandard for electrical to sakthi_murugan86@yahoo.co.in

2259