Why the generating station rating is in KW though the
rating of generators in KVA?
Answer Posted / vittal
generating station main aim is to meet the load which can
be met completlely by the mechanical units or the source of
the prime over ,which must be mention in kw.
where as the rotationg ac machines are rated in kva
because of the losses ie the iron and copper (not on pf)
mention in kva
but even the pf is also mention on the alternator which
means the generator should be operated on that load
ex: if rating of the plant is 100 then if alternator of 0.8
pf is selected the rating of the generator must be 125
| Is This Answer Correct ? | 8 Yes | 0 No |
Post New Answer View All Answers
Define newton's law of viscosity.
State nyquist stability criterion.
1. If 8.35%Z means the percentage impedance of 132kV-line from power company, we will like to confirm its base capacity?
Give some differences between open loop and closed loop control systems.
if we install two earth pits with a clear space of 5m without any interconnection,by checking the digital multimeter will it show continuity between earth pits? If so what would be the approx. value
i have 90kw motor.so i choose connect cable .please what is parameter checked so please give to formula
what kind of technical test that i need to learn because i have an interview tomorrow.. please someone help me..
What is the difference between Generator Differential Relay and Transformer Differential Relay?
How many types of interlocking use in screw type air compressor,make-Kaser(BSD MODEL)?
R=*ΒΆ l/a
What descriptive information does the NEC require to be marked on all conductors?
What is ST and specify its range of voltage.
What are the advantages and disadvantages of open loop control system?
how was your last weekend.
HOW CAN YOU CALCULATE PRACTICAL EFFICIENCY OF A ASYNCHRONOUS INDUCTIONMOTOR OF 7.5KW,& MOTOR IS RUNNING WITH AVOLTAGE OF 410 VOLTS,& TAKING CURENT OF 13 AMPS