1.generator rated as 1000 mva,11kv .8 pf what will 0.8 pf
will indicate?
1.max pf it can supply 2.min pf it can supply
like this 4 options there what is answer.explain

Answer Posted / pillay

i agree with Mr Reddy.
Generator rated at 1000MVA at 0.8 pf 11Kv
In terms of KW the prime mover had been designed for this Gen is 1000 MVA X 0.8 = 800kw, any thing more can destroy your prime mover in the long run
now the alternator part is 1000 MVA AT 11KV
The max amps it can carry is 1000000/1.732/11000= 52.5A /phase
now you can operate the generator at any pf you want as long as you do not exceed 52.5 amps per phase.

Is This Answer Correct ?    7 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

How do you compute voltage drop and cable size over distance?

1761


What is the difference b/w fanuc alpha series 16i and 18i controller. what is stand for i

1594


how to calculation increase capacitor,increase power factor for three phase.

1640


Why reactive power is needed in a power system? How is it being absorbed or delivered by alternators? For reactive power control we are changing excitation but reactive power absorbing or delivering related to stator. How these two are interlinked? i want a detailed explanation with necessary expressions and figures?

1404


a governer in an Ic engine controls the

707






why we use four type of phase angle difference between pimary & secondry winding of a transformer & where we use them?

1629


how to changeover ups in this power failur time?

1534


In motors how many types of cooling systems were used?

1581


will there be any problem by recovering slip from single phase induction motors?

1439


what is the easiest method of short circuit current calculation ? pls. derive with a mathematical example in real life application.

1974


what is the criteria for selection of conductor used for ehv ac electrical dischrge

1611


What will be the voltage regulation of a full load and 0.80 power factor lagging load transformer when a two winding single phase transformer has a voltage regulation of 4.5% at full load and unity power factor?

743


CAN CU XLPE/PVC CABLE BE USED INPLACE OF LOW NOISE SCREENED CABLE? KINDLY GIVE REASONS

1415


tell me some type of questions throught which i can prepare for exam and do my best

1552


How to do cable sizing calculation for 750 A Neutral Earthing resistor for 33kv. the 33kv cable going to swbd. is 630mm2 3 runs.

4323