1.generator rated as 1000 mva,11kv .8 pf what will 0.8 pf
will indicate?
1.max pf it can supply 2.min pf it can supply
like this 4 options there what is answer.explain
Answer Posted / pillay
i agree with Mr Reddy.
Generator rated at 1000MVA at 0.8 pf 11Kv
In terms of KW the prime mover had been designed for this Gen is 1000 MVA X 0.8 = 800kw, any thing more can destroy your prime mover in the long run
now the alternator part is 1000 MVA AT 11KV
The max amps it can carry is 1000000/1.732/11000= 52.5A /phase
now you can operate the generator at any pf you want as long as you do not exceed 52.5 amps per phase.
Is This Answer Correct ? | 7 Yes | 1 No |
Post New Answer View All Answers
How do you compute voltage drop and cable size over distance?
What is the difference b/w fanuc alpha series 16i and 18i controller. what is stand for i
how to calculation increase capacitor,increase power factor for three phase.
Why reactive power is needed in a power system? How is it being absorbed or delivered by alternators? For reactive power control we are changing excitation but reactive power absorbing or delivering related to stator. How these two are interlinked? i want a detailed explanation with necessary expressions and figures?
a governer in an Ic engine controls the
why we use four type of phase angle difference between pimary & secondry winding of a transformer & where we use them?
how to changeover ups in this power failur time?
In motors how many types of cooling systems were used?
will there be any problem by recovering slip from single phase induction motors?
what is the easiest method of short circuit current calculation ? pls. derive with a mathematical example in real life application.
what is the criteria for selection of conductor used for ehv ac electrical dischrge
What will be the voltage regulation of a full load and 0.80 power factor lagging load transformer when a two winding single phase transformer has a voltage regulation of 4.5% at full load and unity power factor?
CAN CU XLPE/PVC CABLE BE USED INPLACE OF LOW NOISE SCREENED CABLE? KINDLY GIVE REASONS
tell me some type of questions throught which i can prepare for exam and do my best
How to do cable sizing calculation for 750 A Neutral Earthing resistor for 33kv. the 33kv cable going to swbd. is 630mm2 3 runs.