A motor works on 30 killo watts.how much ampers will be
required if it works on 440volts?
Answer Posted / gaurang
We Know the Power Equation
P=1.732*V*I*Cosphi
So As per Details
P=30 KW
V=440 Volts
Then,
I=30 KW/1.732*440*0.8
Wher Cos phi=0.8
I=49 A
Is This Answer Correct ? | 5 Yes | 2 No |
Post New Answer View All Answers
why we use single core 630mm2 cable for transformer secondary side
Electrical 'C' license full abbreviation , and full form
the winding of Generator and Motor is star or in delta ? and why
how to calculate IR value of 33KV cable ??
I need to connect a synchronous generator to the grid using automatic synchronization and two circuit breakers (one for synchronization, one for end connection to the grid), how to determinate the required diameter of the cables?
why the rotor current becomes in steady state during high slip region? please verify with equations.
what is the IPC ? & what the uses ?
can anyone explain 11kV 3core cable megger,hi pot test procedure with connection details?
Some times to change of DOR of a motor, interchange of R & B is not effected and RYB take same current, but interchange of R&Y is effected ie change the DOR. My doubt is what is the problem in motor and how it is happen.
WHY BREAKER ARE USED IN SUBSTATIONS?
Brushes are placed at magnetically neutral axis,when brushes reach that point,the armature conductor gets shorted,but it can be seen that the dc supply is also shorted,wont that get damage? help me plz
redundant connection in contactor?
why we used dc supply for field in dg set
hai friends i have BSNL JTO exam on next month so if any body have model question paper or give preparation tips to my mail id kumar4486@yahoo.co.in this will helpfull for my future .plz & thank u by kumar
what is meant by LCR meter? where its useful ?