Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

How to make vector group test of transformer?

Answer Posted / mprajaneb

vector group testing: Assume that the terminals of the
primary windings are denoted as A, B, C in counter clock
wise direction and for secondary winding as a, b, c also in
counter clockwise direction. short circuit the terminals A
and a, and apply LT supply to the three terminals of HV
(Aa, B, C)
For Dy1 transformer: VbB = VcB and VbC grater than VcC.
For Dy11 transformer: VbC = VCc and VBb less than VcB.
For Yy0 transformer: VBb = VCc and VbC = VBc.

Is This Answer Correct ?    4 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

how to generator maintenance (A Check, B check,Etc)

2349


When we need up only in o/p 440v, so why we use directly in 11kva in input?

1752


What is the difference between a 3 winding and 2 winding Potential Transformer

2339


What are differences between Voltage, EMF & Potential difference ?

2069


When steam condenses and becomes water at the same temperature, the specific heat for the process in kJ/kg k is

1184


Can RCD's used to protect the VVVF drive if not why.

2205


How isolater function when installed inelectrical 440V wiring

2293


What is George phenomena to start the synchronus machine?

4206


what is the difference between ups & inverter

7362


Pl. share your experience about industrial-electronics repair of machine tool.

1947


An 8 pole, 50 Hz, 3-phase IM is loaded to a poing where pull out torque will occur. The rotor resistance per phase is 0.3 ohm and motor stalls at 650 rpm. The rotor reactance at stand still is A 2 ohm B 1.25 ohm C 3.15 ohm D 2.25 ohm

2364


Hello sir i m student of gtu .what is idp.

2240


why in a swquence network representation, the negetive sequence generated voltage is taken as zero?

2066


how to check regenerative load in drived motor

2302


15hp motor wound by 0.9mm & 0.95mm magnet wire. at no load test it draw 4.2A current. Another motor with same condition draw 9.2A current. How can that occur? pls help

1624