Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

Please explain open transition and closed transistion
system in Star delta Starter?and also the state difference
of both?

Answer Posted / dave

worked for carrier a/c 35 years. in a standard open
trastion when charging from star to delta the motor
effectively slows momenatrily for a 1/5 of a scond. closed
traansition this does not happen ,the change from star to
delta is less noticeable.closed transiontion has a fourth
contactor and resistor bank to prevent that 1/5 of second
power loss to the windings .I need some wiring digrams of
closed transion staters to show the tecs how this works

Is This Answer Correct ?    5 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Anyone who can recommend an equivalent to Envirotemp FR3 of Cooper?

2020


Why generation voltage in thermal power plant is between 11kv to 33kv?

1077


what are the different methods for the starting of a synchronous motor.

1170


how to discharge 3 phase power factor correction capacitors

2501


Dear Mr B C pal...Can you plz. put some light on principle of operation of Z-Ct in conjunction to its use with 1Cx1000Sqmm HT Cables & Directional Ground Fault / Over Voltage Relays...Regd..Parag v K 9899115632

2813


How to calulate Locked rotor amper(LRA) for compressor type motors?

1824


Where servomechanism is used?

1160


What are the different circuits in thermal power plant?

1226


What is the difference between the impedance percent and impedance voltage ?

2273


Sir,In our company there are 3 caterpillar make(capacity:(1) 3.3KV,2.5MW(2)3.3KV,2.5MW & (3)3.3KV,1.9MW) & 1 deutz make (capacity:11KV,3.8MW)gas engines utilised,all are running in paralell. There are three transformer utilised,(1) 6.25MVA,3.3KV/22KV,Impedence voltage:6.7% used for two generator,both are 2.5MW(2)5.5MVA,3.3KV/22KV,Impedence voltage:7.2% used for one generator of 2.5MW & (3) 5.5MVA,11KV/22KV,Impedence voltage:7.8% used for one generator of 2.5MW.all generator breakers capacity of 1250Amps. Sir,I want the details of fault level calculation of generator,transformer individually & for whole system. If you require any information from me.feel free for contact me sir.pl.send the answer of my question as the earliest as possible.

2176


at work i have a genertor/alternater what is the easyest way to work out if it is dc or ac?

1923


whats the differece between Exd and Exe

5025


What is Diff btw Fire Alarm & VESDA System???

2444


write circuit diagram for a motor rotate in forward direction once it started and when pressed the same button it should rotate in anticlockwise.

2612


how did the testing of protection relays done through current injection

2137