Why the rating of the HT breakers are in 1250 Amp, while
the load on the breaker is around 50 Amp. ?
Answer Posted / sobhuza, za
For those who this my answer (Answer 2) is incorrect. It is
important to remember that HT circuit breaker has two
current ratings. One is the continuous current rating. The
other one is the maximum fault breaking rating that the
breaker can carry for about say 2 seconds. The former is
what the question is about. The latter is in kA range
typicaly 25kA or so. Therefore 1250A is just a normal load
current that the circuit breaker can carry.
| Is This Answer Correct ? | 17 Yes | 3 No |
Post New Answer View All Answers
explain Density
what is rating boiler
What is instrumental error?
True or false question. 1.The fuse provide phase and neutral 2.power loss in electrical circuit can take place in (resistance or inductance or capacitance). 3.two phase system each phase has separated by a phase difference of (90 or 180 or 270 or 45). 4.3 phase balanced star connected load neutral current shall be (line current or phase current or zero or unity)
What are the two major types of control system?
if there is nutral in phase why we use earthing wire and grounding? even at fault condition the fault current flows to neutral (it is a lower path)
WHY NUTRAL GROUND SYSTEM USED IN 33KV SYSTEM
What is Auto Mains Failure Panel & Auto Synchronizing Panel
How to protect a Dosing pumps/any sensitive equipment (single phase) from surge protection inside a food factory.
wat is meant by PX class in ct?
how to erect roof control panel?
Define norton equivalent circuit?
can u please mail me the syllabus for GET exam for damodar valley corporation?
why dc is used in control circuit for mv & hv switchgear instead of ac
I am experienced with house and industrial wiring but I don't have any licence how can I apply an licence and which type of licence i can get i didn't complete deee just only experience