Why the rating of the HT breakers are in 1250 Amp, while
the load on the breaker is around 50 Amp. ?
Answer Posted / sobhuza, za
For those who this my answer (Answer 2) is incorrect. It is
important to remember that HT circuit breaker has two
current ratings. One is the continuous current rating. The
other one is the maximum fault breaking rating that the
breaker can carry for about say 2 seconds. The former is
what the question is about. The latter is in kA range
typicaly 25kA or so. Therefore 1250A is just a normal load
current that the circuit breaker can carry.
| Is This Answer Correct ? | 17 Yes | 3 No |
Post New Answer View All Answers
role of europe union in UK safety legistlation (electrical safety)
What is the phase relationship between the primary and secondary voltages of a transformer?
how braking & making capacity of circuit breaker are calculated?
If we impress a dc voltage of 230 V on an unloaded 230 V, 50 Hz transformer it wi A give high secondary voltage B burn out C give secondary voltage as per K D none of these
Transmission voltage is kept 11KV,33KV,66KV,132KV,220KV due to form factor. What happen to 400KV and 765KV transmission voltage?
Give some differences between open loop and closed loop?
What is the minimum value of hfe for the oscillations in transistorized rc phase shift oscillator?
how to find number of run cable laying[LT side] for transformer & alternator secondary side? [above condition for getting output power transformer to main panel side] give the example.
what is the practical application of full adder circuit?
Explain the terms real power, apparent power and reactive power for ac circuits and also the units used.
how to produsing geretor power
how we can come to know that motor winding resistance which showing by DMM is right or wrong???is there any chart or something that we will compare & check???
PLEASE TELL ME ABOUT QUESTION PAPER OF UPCL ENTERENCE EXAM.
how to calculate insulation level of transformer?
what is saturation kit?which use above 15 kw motors panel side.