how much loading in terms of ampere can put on 5 MVA,33/11
KV TRANSFORMER having rated current 263 Amp ?????????
Answer Posted / pravin
Actually it depends upon designer. If we asked designer to
designed for 125% overload, he will provide cooling per
current loading on 125% overload to restrict Hot Spot Temp.
of the winding & Top oil temp. respective to max. ambient
temp.
In this case, we can provide loading of 437A in
terms of ampere on top rating with Hot spot temp & top oil
temp in control on top rating. Actually transformer has
three rating OA/FA/FA. If this transformer is OA/FA/FA then
we can provide this loading.
If it is self cooled then 263A is max. loading.
| Is This Answer Correct ? | 5 Yes | 1 No |
Post New Answer View All Answers
what is ps impedance test
What is shutdown of electrical sub station?
why the pf of semiconductor device is improved the electrical devices
Write down the name of 2 lady Bir Pratin of Bangladesh
WHY RATING OF VCB NOT LESS THAN 630A
why voltage form factor of PT are increase , when it is ecpected heigher spikes in system. how it is calculated.
how to compare with Relay settings for HT< panels, RMU panel, and PSS CSS transformer?? 1) Load amps, 2)Tripping time, 3) CT ratio, 4)Cable size 5) Transformer KVA rating 6) transformer full load amps
actually i can't understand what is 3dB ? and it's really not clear to me.please any one let it me be cleared.
Difference between ac parallel circuit and ac series circuit?
What is the cut-off rate?
Explain how you decide what size of electrical wire do you need?
what is induction furnance? how many phase supply given io its coil for 15 or 20 ton furnance?
why the India electrical supply transmission loss is high when compare to us
which network topology offers the greatest level of tolerance?
In a power conditoining unit (inverter) of a solar plant when we measure the d.c. current fed by different strings of solar plates to inverter, the current in the negative wire is less almost by 1 ampere to the current in its positive wire say current in positive wire 5 A , then current in negative wire of the same string is 4 A. Since the current entering should be equal to current leaving then why the current is noticably less in negative wire.