Why not implimenting power factor in Diesel generator
Answer Posted / ravi
In case we correct the existing P.F. in case of DG set by
putting capacitor panel across DG set, then there is no
harm until the cicuit draws inductive or lagging P.F. . But
in case it starts drawing leading P.F. due to addition of
excessive capacitors across D.G. set then the output
terminal voltage would be higher than the induced voltage.
so it is not desirable to operate cap. panel across DG set.
| Is This Answer Correct ? | 8 Yes | 1 No |
Post New Answer View All Answers
What are your future plans for the company if permanently employed?
What is Tachometer used to measure?
Explain M Var? Which types of problem occurs when reactive power increase at the time of full load of plant and at the time of synchronize of plant?
what is droop control?
harmonics filter
what is the stear deltaprinceple?
Can anyone explain me about the RLC based Impulse high voltage generator and how to and operation of Series resonant High voltage reactor...?
how to select battery for 15 KVA UPS with formula
How the circuit breaker is selected for Induction motor of 100 kW, 415 volt, 0.85 power factor, 0.95 efficiency ?
what happen as when voltage drop(or may decrease) ? in case of atomic base theory?
A Generator is in running condition and Rotor earth fault alarm is coming.How to check on line(i.e in running condition) whether there is actual earth fault in rotor or not.
When will you multiply and devide with derating factors to the actual value while sizing the cable?
what is cathodic protaction?
WHAT IS MEANT BY TV TERMINAL IN 500MVA TRANSFORMER?
When the relative speed between the magnetic fields of stator and rotor does is zero under steady state operation?