Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

Why VCB and SF6 breakers to be used in HT used by cant ACB
of higher rating to be used for 11kv and 33kv.

Answer Posted / baskaran.r

in an acb the distance between terminals are fixed for 415
volts. for higher voltages this need to be much larger.
there are some makes acbs are available in 3.3 kv with
increased gap to the tune of 2 feet. For higher voltages the
gap required will be very much higher.arc handling will be
impossible in higher voltages

Is This Answer Correct ?    17 Yes 10 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What is an ideal transformer?

1175


What will happen if we on 200kvr capacitor bank(11kv in bus)If there is low load on transformer (1.5 mva 33/11 kv)

1568


for what voltage will reactive power be largest in 380 kv line : a) 375kv b)380kv c)385kv

1481


primery try cell?

2205


What is the tests required for a 132 kV, 400 kV , 765 kV for a Circuit Breaker and Power Transformer before commissioning ?

1594


why is a power transformer used only occasionally?it is used to step up at generating stations?and that needs to be done all day long !!!!!!!

1872


what is the transmission loss for electrical supply? specifically a large shopping complex where the grid is half KM away, what will the % of transmission loss? is there any transmission loss for captive unit generation for above set? thanks

1981


in our all power plant have connected in grid and grid voltage and plant voltage is same, but as per as electrical concept the power will transmit from high potential to low potential but here altough same,then how power transmit from power plant to grid.

2339


How we can calculate the consumption in kwh of motor on basis of kw @100% load, @50% load & @ no load.

2796


How much ph is maintained of water electrolyte which is used in LRS for 1200 kw slipring induction motor ?

1770


what is the ms flat constant for calculating earth mat design calculation?

2518


hi everybody how to design string combiner box (scb) internal parameters like bus bar and spd (surge protection device and fuse which place to set that,and also bus bar one particular cross sectional how much heat generated and how much power loss tell me Clearly and briefly

1993


Is there any specialised book to refer about fault level calculation both in MV and LV side??

2071


please send me jindal previous aptitude and technical question and answer.my email id is deep_raj@live.com

1973


how test transfomer(3 phase75kva) by megger

2122