can we load Power capicitors on DG sets?
Answer Posted / amarnath
YES ! The DG Rating is always defined in KVA @ 0.8 Pf Lag.
Hence for optimum utilization of the DG power, it will be
best to have the PF regulated to 0.8 PF Lag. However, care
must be taken not to let the PF go into LEAD condition as it
can lead to instabilty of the system voltage. Suggest to
conduct a detailed load study and opt for Automatic PF
Improvement Relay panels wherein the DG target PF can be set
@ 0.8 and for EB the target setting can be 0.95 Lag or above
. (definitely not LEAD)
Is This Answer Correct ? | 3 Yes | 0 No |
Post New Answer View All Answers
What are the material used for inductance coil?
What are the internal and external faults?
Proviiding the Dedicated N earth and individual Body Earths ,Finally these all looped /Now my Question :- will it not harm in case of Transformer Fault current flows in Dediacted N Earthing to Looped Body Earthing.
what exactly commisioning work does in electrical site work... LT side?..
how to select correct size of power cable for inverter duty motor
area control error
how to prepare the technical test
1 hp is equal to how much watt?
On a 6 KVA UPS we have to provide a DC MCB for Battery bank of 16 nos (12 V 42 AH). What Shall be the current rating of DC MCB ?
The power supplied to a 50mH inductor from a 120V, 60Hz source will be
If the line voltage is reduced to 75% of its rated value then by what percentage current will reduce ?? 75% 25% 50% no change and why ?
How will you justify IR value and Charging voltage of any motor,transformer and Cables.......???? . . . . . . . . Plz tell me any body Baljeet Singh, engineer_89@refiff.com
what is the differebt between ac and dc fuse?
Why is ignitor used in sodium vapour lamp
how can found motors folt current ? how can disided circuit breakers caoicity and breaking capicity ?