can we load Power capicitors on DG sets?
Answer Posted / amarnath
YES ! The DG Rating is always defined in KVA @ 0.8 Pf Lag.
Hence for optimum utilization of the DG power, it will be
best to have the PF regulated to 0.8 PF Lag. However, care
must be taken not to let the PF go into LEAD condition as it
can lead to instabilty of the system voltage. Suggest to
conduct a detailed load study and opt for Automatic PF
Improvement Relay panels wherein the DG target PF can be set
@ 0.8 and for EB the target setting can be 0.95 Lag or above
. (definitely not LEAD)
| Is This Answer Correct ? | 3 Yes | 0 No |
Post New Answer View All Answers
Hi, This is Laila. I am selected for syndicate bank interview. Could you please share your views and the questions asked if you have faced the interview My email id is laila_honey09@yahoo.com Please send as fast as u can.Thank You Thanks... Laila.
How to address the servo drive for motor
What is the general system requirement of alternator?
Salient pole alternator is more stable, why?
How to select, design,size & calculate for 11 KV/33KV/66KV/132KV/220 KV/440 KV circuit breaker for HT side of transformer protection/HT distribution protection?
why ss stablity limit is more transient stablity limit?
What is the approximate value of stacking factor?
how to failure indution motor insulation & how to improve heat in motor insulation
What is the function of NER and NET?
If UG power cable both ends are to be earthed or what? If not why?
How to find out damper winding failure for synchronous machine?
Who are the manufactures those manufacturing 3Cx2.5sqmm FRLS cables. I heard about FRLS technology adopted only in wires useful for wirings
What is the difference between diode and a transistor in terms of the direction of current flow?
i have been tasked with a design of protection, metering and control(PMC) relay panel extension to accommodate all PMC relays.There is an already existing panel where this one will be built.What are the design aspects for this kind of project? thank you.
There is any especial requirement for motor to drive through with VFD?