we are using three transformer 33000/430 vac for three
separet block.all three transformer have three LT panel
separetly. can be Interconnected all three panel through bus
coupler. this is permissable or not by state electricity board.
Answer Posted / manoj dubey
apart from above said pl. also check for your switchgear
rating for fault current as you parallel the system your
system fault current level will increase so your system
should be able to take care of it.
| Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
why it is not advisable to run low rating (19KVA) DG sets in parallel for long durations even though they are provided with droop ckts (QDC)
How you give clearance to a spare feeder.
How seriving & testing of the HT & LT breakers are done. What are the standard Ir values on which we can come to know the test is passed or failed?
defination of controlled shunt reactor
What is Percentage impedence of a transformer? why it is expressed at a percentage? what is the importance of percentage impedence in case of a transformer?
What are the advantages of thermal power plant?
what is the current density of copper & alluminium.
What is touch potential and step potential?
Why we specify TNC switch with 1NO 1NC ,2NO 2NC ? how we get connection.?
i have to install a HT panel, what components, I have to use in this and what will the diagram of that diagram,please tell me each and everything.
why swityard is necessrry requirement in any bis power distributin systems?
while doing high potential for 11KV 3 core cable how much leakage current will obtain?, what will be acceptance value?
What is the earth treantment procedure?
i have a 4 Mva transformer 34.5 kv / 480-277 v and i used 2 parallel 3200 amp bus duct for the secondary feeder using 3 ply of bus bar ( 3/8" x 5" ) as a common where the flexible link terminated and 6300 amps breaker for the main, the lower bus duct reaches 70 degrees and the upper bus duct reaches 55 degrees when i used thermal scanner. why the temperature is not balance when the load reaches 3600 amps.
diameter of cable and core is doubled then the value of capacitance is