we are using three transformer 33000/430 vac for three
separet block.all three transformer have three LT panel
separetly. can be Interconnected all three panel through bus
coupler. this is permissable or not by state electricity board.
Answer Posted / sgthakur
Obviously ths is permissible.
1. carry on the PI test of each trans.It should not be less
than 2.00
2.Kva rating must be same
3 Percentage impdence must be same if diff .,parallaling
can be done but trans load shsring may be diff.
4 vector Gr.must be same
5If the Trans. HT source coming fr. diff. source, before
connecting them parallel phase ballancing and phase
seq.test must be done.
6.Other paralling condn. ie freq., voltage must be same as
usual.
7. On LT side trans. tape must be kept in same pos.
| Is This Answer Correct ? | 5 Yes | 0 No |
Post New Answer View All Answers
How will A Medium voltage circuit breaker(11 kV voltage level) operate under short circuit fault condition whether It is having short circuit release like Low voltage circuit breaker or relay should be given?
types of central Air conditioner plant?
hi i will D.E.E.E.is completed pls send rrb diploma old qustion papaer sent in my e mail. i.d.
The series field winding has low resistance while the shunt field winding has high resistance. Why?
What are capacitive,resistive,inductive surge absorbation? What is ferranti surge absorber? What is lagrangian cost? What is Px operator?
y we use neutral,all r told its used to for closed path..k its a just used to closed path,in a transmission line y we put same conductor used n both phase and neutral..if we use less than phase conductor in neutral mean we ll reduce cost its right r wrong..if we use mean any problem occur in transmission line..
what irequirment need to be followed when working on live equipment
What are the major reasons for balancing hydro-thermal mix?
what are the applications of transistors with low dc gain, high dc gain and medium dc gain( beta)?
How each of the following losses occur in d.c machines (i) copper (2)core (3) windage (4)friction please help me
Name one of major transformer company in KSA ?
I want to know how to calculate the size of electricity cable in building?
What is the loss of transformer of 220kv/11kv, 63/80 MVA and 18.05% impedance
How can calculate the rating of a alternator for a given specific load with formula
As we use capacitor bank in 3ph ckt to improve PF, can we use capacitor in single ph domestric use, in house we have Fan,Mixer,electric cooker,iron,tube choke they also lag the system,because it is inductive load. if it is possible to improve PF of single ph system-- if yes- type of capacitor to be used,connection diagram, working in detail. if no-- list it.