What will be the total current for 300kva UPS if it runs on
40 to 45 percent load. Is there any formula for to
calculate the exact load.
Answer Posted / thowsif_emerson_csm team
For 300 KVA the Full load Current=KVA*PF,
i.e 300x.8=240000 Watts.
we know in 3 Phase Circuits,
P=1.732x V x I x Pf,
I=P/1.732xV x Pf,
I=240000/1.732 X 440 X 0.8,
Full Load Current, I =240000/609=394 Amps,
The Load Current @ 40% is 394*.40=158 A(Total Load Current).
The Load Current @ 45% is 394*.45=177 A(Total Load Current).
So load current at 40% Load is 39*.40=15.6 A/Phase Amps.
| Is This Answer Correct ? | 11 Yes | 6 No |
Post New Answer View All Answers
IN SINGLE PH TRANSFORMER IF LEKAGE IMPEDANCE DROP IS NEGLECTED ,THE FLUX IN THE MAGNETIC CORE and the lekage flux linking a winding are a)proportional to the applied v to the winding i respectively.
Brief me about maintenance planning & sheduling of machine tool.
Explain the different methods used in the choice of rotor slots for reduction of harmonic torques in an induction motor.
How PADO software increase the efficiency of power plant?
What is the importance of earthing?
What is deference between MCB & MCCB & ISOLATOR
Why the standard of ambient teperature mentioned as 40 degree celcius in machines.
What does ampere turns shows?
what's the difference between 'shaft power demand' and 'BHP' , when we consider electrical load list.
Is there any type of starter for DC motor other than two point,Three point and Four point starters?
Pls tell me whether we can use EN3A material for shafts of Permanent magnet alternator.What will be the effect of magnetic and nonmagnetic material for shafts on magnetic properties of PM rotor .
Could Please Explain briefly. Why used stabilizing resistance series with High impedance bus differential protection relay.
direction of tarbine& genrator
why constant voltage transformer should be start without load? and if started then what will happen?
why does connected a indutor with mnsformeretering core of current transformer ?