Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

What will be the total current for 300kva UPS if it runs on
40 to 45 percent load. Is there any formula for to
calculate the exact load.

Answer Posted / thowsif_emerson_csm team

For 300 KVA the Full load Current=KVA*PF,
i.e 300x.8=240000 Watts.

we know in 3 Phase Circuits,

P=1.732x V x I x Pf,

I=P/1.732xV x Pf,

I=240000/1.732 X 440 X 0.8,

Full Load Current, I =240000/609=394 Amps,

The Load Current @ 40% is 394*.40=158 A(Total Load Current).

The Load Current @ 45% is 394*.45=177 A(Total Load Current).


So load current at 40% Load is 39*.40=15.6 A/Phase Amps.

Is This Answer Correct ?    11 Yes 6 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what is the function of impulse relay

2523


ASTM D 3455 - Standard Test Methods for Compatibility of Construction Material with Electrical Insulating Oil of Petroleum Origin has been used for Testing Transformer Oils with a product placed in it. Aged Control Oil has a Power Factor of 0.032% at 100°C. Aged Oil with a Test component has a Power Factor of 0.093% at 100°. Is this increase acceptable? If not why? How much increase is acceptable?

2024


Name of the relay of low lub oil presuure in DG sets

2053


What will be electrical cost per sqft for IT building (basebuild and fitout)and for residential township?

1936


What is the dc grounding system and what is diff between AC/DC grounding system?

2120


Which contains in POLE ASSEMBLY of a 11KV Kirloskar-make SF6 (Model No-FP620A12)? Will u clarify with drawing?

2177


I am getting above 60 V as open delta voltage against single phase unit ICT at tertiary delta formed and ICT getting trippped on NDR. ICT tested and found in order. PTs provided on tertiary are tested and in order. what may be the reason?

1966


what is metering cum synchronizing panel and how it is used?

4648


when we have to purchase the transformer by own i.e how much load will preferred HT connection?

1674


what is the main difference between power devices and signal devices

2191


any one guide me to reduce the power factor of diesel Generator from 0.97 Leg to 0.8 Leg.with out any change in my load.

1677


how does the thyistor work in dc drive?

1986


area control error

1738


What will happen if the d.c. Shunt motor opened accidentally running on no-load has its shunt field winding?

1476


In the Variable Voltage Variable Frequency Drive, how the Voltage and Frequency varied ? Is it varied in the Inverter part of the Drive ? Please give us supporting document if any.

1953